ACH580 E-Clipse bypass and packaged drive user manual
61
Parameters
Group 04: Fault Log
0307
FLT WORD 3
—
b0: 1 = EFB 3
b1: 1 = Open motor phase
b2: not used
b3: not used
b4: 1 = Control board
temperature
b5: not used
b6: not used
b7: not used
b8: 1 = RBIO ID error
b9: 1 = Stack overflow
b10: 1 = Timed scan
overflow
b11: 1 = Serial flash corrupt
b12: 1 = Unknown drive
b13: 1 = Unknown bypass
b14 - b15: not used
0
Bypass fault status,
word 3
0308
WRN WORD 1
—
b0: 1 = Input phase A loss
b1: 1 = Input phase B loss
b2: 1 = Input phase C loss
b3: 1 = Auto transfer active
b4: 1 = External Comm
Error
b5: 1 = Permissive
b6: 1 = PCB Temp
b7: 1 = Drive Setup
b8: 1 = Bypass run delay
b9: 1 = Motor Temp
b10: 1 = Underload
b11: 1 = Bypass disabled
b12: 1 = Drive link error
b13: 1 = Drive test
b14: 1 = Drive 1st start
needed
b15: 1 = Low input voltage
0
Bypass warning status,
word 1
0309
WRN WORD 2
—
b0: not used
b1: not used
b2: Override 1
b3: Override 2
b4: 1 = Interlock 1
b5: 1 = Interlock 2
b6: 1 = Interlock 3
b7: 1 = Interlock 4
b8: 1 = Mode auto lock
b9: 1 = Mode local lock
b10: 1 = Comm config error
b11: 1 = FIG parameter
configuration
b12: 1 = Drive faulted
b13 - b15: not used
0
Bypass warning status,
word 2
Group 04: Fault Log
Code
Name
Resolution
Range
Default
Description
0401
LAST FAULT
1
3001 - 3999
See 'Faults' page
0
Last fault declared
0402
F1 TIME 1
1, days ago
0 - 65535
0
Time since last fault, days
0403
F1 TIME 2
2, ago
00:00:00 - 23:59:58
0
Time since last fault,
hr:min:sec
0404
F1 VOLTAGE
1V
0 - 1200V
0
Input voltage at last fault
0405
F1 CURRENT
0.1A
0.0 - 6553.5A
0
Motor current at last fault
0406
F1 EVENT 1
—
See parameter 501
0
Last event status before last
fault
0407
F1 E1 TIME
2, before
00:00:00 - 23:59:58
0
Time before last fault of last
event: hr:min:sec if time < 1
day
1, days before
0 - 9999
days if time >= 1 day
0408
F1 EVENT 2
—
See parameter 501
0
2nd to last event status before
last fault
Group 03: Status
Code
Name
Resolution
Range
Default
Description
Summary of Contents for ACH580 Series
Page 2: ......
Page 11: ...ACH580 BCR BDR VCR VDR E Clipse Bypass Drives 1 200 HP ...
Page 35: ...26 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 43: ...34 ACH580 E Clipse bypass and packaged drive user manual Start up ...
Page 67: ...58 ACH580 E Clipse bypass and packaged drive user manual Application macros ...
Page 193: ...184 ACH580 E Clipse bypass and packaged drive user manual Fieldbus adapter ...
Page 207: ...198 ACH580 E Clipse bypass and packaged drive user manual Diagnostics ...
Page 229: ...220 ACH580 E Clipse bypass and packaged drive user manual Technical data ...
Page 231: ...ACH580 PCR PDR Packaged Drives with Disconnect 1 200 HP ...
Page 243: ...234 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 256: ......