80
ACH580 E-Clipse bypass and packaged drive user manual
Embedded fieldbus
Refer to the figure for the System mode diagram.
Fieldbus communication selection
To activate the fieldbus communication, set parameter 9802 COMM PROT =
• 1 (STD MODBUS).
• 2 (N2)
• 4 (EXT FBA) - See
on page
• 5 (BACNET)
Note:
In System mode, the Building Automation System writes to either the bypass
or the drive, through two logical nodes. A common physical port supports both
nodes. Group 58 is used to configure (i.e., baud rate) and diagnose the common
physical port. Group 58 is also used to configure (i.e., MAC ID and Device Object
Instance ID) and diagnose the drive logical node. Group 50 is used to configure
(i.e., MAC ID and Device Object Instance ID) and diagnose the bypass logical node.
E-Clipse
ACH580
1625 = System Mode
Bypass
(Group 50)
Drive
(Group 58)
Control:
- Start / Stop
- Run Permissive
- Start Interlock 1…4
Status:
- Ready
- Enabled
- Started
- Running
Control:
- Reverse
- Ext 1 / Ext2
- Reference 1
- Reference 2
Status:
- Actual Values
Summary of Contents for ACH580 Series
Page 2: ......
Page 11: ...ACH580 BCR BDR VCR VDR E Clipse Bypass Drives 1 200 HP ...
Page 35: ...26 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 43: ...34 ACH580 E Clipse bypass and packaged drive user manual Start up ...
Page 67: ...58 ACH580 E Clipse bypass and packaged drive user manual Application macros ...
Page 193: ...184 ACH580 E Clipse bypass and packaged drive user manual Fieldbus adapter ...
Page 207: ...198 ACH580 E Clipse bypass and packaged drive user manual Diagnostics ...
Page 229: ...220 ACH580 E Clipse bypass and packaged drive user manual Technical data ...
Page 231: ...ACH580 PCR PDR Packaged Drives with Disconnect 1 200 HP ...
Page 243: ...234 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 256: ......