![background image](http://html.mh-extra.com/html/abb/ach580-series/ach580-series_user-manual_2512166.webp)
ACH580 E-Clipse bypass and packaged drive user manual
157
Embedded fieldbus
The bypass status word is defined in table below. The drive status word depends on
the profile selected and does not change when bypass parameter 1625 = DRIVE
ONLY or SYSTEM modes (see drive manual).
BYPASS STATUS WORD
Bit
NAME
Value
Description
Comments
0
READY
1
Bypass is ready to receive
start command
0
Bypass is not ready
1
ENABLED
1
External Run Permissive and
Start Interlock signals
received
0
External Run Permissive or
Start Interlock signals missing
2
STARTED
1
Bypass has received start
command
0
Bypass has not received start
command
3
RUNNING
1
Motor is running
0
Motor is not modulating
4
FIELDBUS_LOCAL 1
Bypass is in fieldbus local
mode
Field bus is controlling all
inputs that can have COMM
setting.
0
Bypass is not in fieldbus local
mode
5
FAULT
1
Bypass is in fault state
0
No faults
6
WARNING
1
Warning is on
0
No warnings
7
Reserved
8
REQ_CTL
1
Control word requested in this
channel
This bit set indicates that
the bypass is expecting at
least one control bit from
the serial channel.
0
Control word not requested
9
OVERRIDE
1
In override
Override 1 or override 2 is
active
0
Not in override
10
POWERED_UP
1
Powered up
Input voltage has passed
minimum level beyond
which normal bypass
operation can proceed
including writing of
parameters from the field
bus.
11
MODE
1
Bypass mode
0
Drive mode
12
PANEL LOCAL
1
Bypass in local (Hand or Off)
0
Bypass in Auto
13...15
Reserved
Summary of Contents for ACH580 Series
Page 2: ......
Page 11: ...ACH580 BCR BDR VCR VDR E Clipse Bypass Drives 1 200 HP ...
Page 35: ...26 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 43: ...34 ACH580 E Clipse bypass and packaged drive user manual Start up ...
Page 67: ...58 ACH580 E Clipse bypass and packaged drive user manual Application macros ...
Page 193: ...184 ACH580 E Clipse bypass and packaged drive user manual Fieldbus adapter ...
Page 207: ...198 ACH580 E Clipse bypass and packaged drive user manual Diagnostics ...
Page 229: ...220 ACH580 E Clipse bypass and packaged drive user manual Technical data ...
Page 231: ...ACH580 PCR PDR Packaged Drives with Disconnect 1 200 HP ...
Page 243: ...234 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 256: ......