ACH580 E-Clipse bypass and packaged drive user manual
E-Clipse bypass functions overview
Bypass Not Fault (7) [BYP NOT FLT]
If configured for
Bypass Not Fault,
the relay is energized during normal operation.
The
Bypass Not Fault
relay is de-energized when power is removed from the
system, a bypass fault has occurred or when the bypass motor overload/underload
protection has tripped. The specific nature of the fault is indicated on the bypass
control panel display.
Bypass Warning (8) [BYPASS WRNG]
If configured for
Bypass Warning,
the relay is energized when a bypass warning is
present. The specific nature of the warning is indicated on the bypass control panel
display. The
Bypass Warning
relay is de-energized during normal operation.
Drive Fault (9) [DRIVE FAULT]
If configured for
Drive Fault,
the relay is energized when a drive fault has occurred.
The specific nature of the fault is indicated on the drive control panel display. The
Drive Fault
relay is de-energized during normal control panel.
Drive Not Fault (10) [DRV NOT FLT]
If configured for
Drive Not Fault
, the relay is energized during normal operation. The
Drive Not Fault
relay is de-energized when power is removed from the system, or
when a drive fault has occurred. The specific nature of the fault is indicated on the
drive control panel display.
Drive Warning (11) [DRIVE WARNING]
If configured for
Drive Warning,
the relay is energized when a drive warning is
present. The specific nature of the warning is indicated on the drive control panel
display. The
Drive Warning
relay is de-energized during normal operation.
Override (12) [OVERRIDE]
If configured for
Override
, the relay is energized when Smoke Control Override or
Advanced Override mode is selected and de-energized in all other modes. The
Override
relay is de-energized during normal operation.
Bypass Hand (13) [BYPASS HAND]
If configured for
Bypass Hand
, the relay is energized when the motor is running in
Bypass Mode and Hand (manual operation) is selected. The
Bypass Hand
relay is
de-energized when Bypass Auto or Bypass Off are selected.
Bypass Off (14) [BYPASS OFF]
If configured for
Bypass Off
, the relay is energized when the bypass control mode
Off
is selected. The
Bypass Off
relay is de-energized when either Bypass Auto or
Bypass Hand are selected.
Bypass Auto (15) [BYPASS AUTO]
If configured for
Bypass Auto,
the relay is energized when the bypass control mode
Auto
is selected. The
Bypass Auto
relay is de-energized when either Bypass Off or
Bypass Hand are selected.
Summary of Contents for ACH580 Series
Page 2: ......
Page 11: ...ACH580 BCR BDR VCR VDR E Clipse Bypass Drives 1 200 HP ...
Page 35: ...26 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 43: ...34 ACH580 E Clipse bypass and packaged drive user manual Start up ...
Page 67: ...58 ACH580 E Clipse bypass and packaged drive user manual Application macros ...
Page 193: ...184 ACH580 E Clipse bypass and packaged drive user manual Fieldbus adapter ...
Page 207: ...198 ACH580 E Clipse bypass and packaged drive user manual Diagnostics ...
Page 229: ...220 ACH580 E Clipse bypass and packaged drive user manual Technical data ...
Page 231: ...ACH580 PCR PDR Packaged Drives with Disconnect 1 200 HP ...
Page 243: ...234 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 256: ......