ACH580 E-Clipse bypass and packaged drive user manual
67
Parameters
Group 17: Override 2
1631
DRV/BYPASS
1
0 = KEYPAD
1 = DI5
KEYPAD
(0)
Selects source for drive/bypass
mode command.
(0) Keypad – The drive/bypass
mode selection is made
from the bypass keypad
(DRIVE or BYPASS select
keys).
(1) DI5 – The drive/bypass
mode selection from the
bypass keypad is disabled
and selection is made from
the digital input. When DI5
is energized the system is
set to bypass mode.
1640
PASS SET
0 – 65535
0
Sets the passcode that is
compared against parameter
1618- PASS CODE. Passcode
required to open.
1641
PASS CNFRM
0 – 65535
0
Confirms the setting of
parameter 1640 - PASS SET.
1642
ABB ACCESS
0 = LOCKED
1 = OPEN
LOCKED
(0)
Locks access to factory only
parameters and factory debug
tool. Passcode required to open.
1643
FB LOCK
0 = LOCKED
1 = OPEN
OPEN
(1)
• Allows Fieldbus writing of
parameters. Applies to
embedded and FBA.
• Does not affect control of the
bypass over the fieldbus.
• Does not affect bypass
parameters in group 53- FBA
DATA OUT.
• Does not affect writing of
parameters to the drive.
Passcode required to open.
1644
DNLD LOCK
0 = LOCKED
1 = OPEN
OPEN
(1)
Allows locking of program and
serial flash downloads.
Passcode required to open.
Group 17: Override 2
Code
Name
Resolution
Range
Default
Description
1701
OVERRIDE 2
1
0 = NOT SEL
1 = DI5
2 = COMM
NOT SEL
(0)
Selects source for override 2
command.
1702
PERMSV OVR
1
0 = ACKNOWLEDGE
1 = DISREGARD
DISREGARD
(1)
Acknowledge or disregard
permissive during override 2.
1703
INTLK1 OVR
1
0 = ACKNOWLEDGE
1 = DISREGARD
DISREGARD
(1)
Acknowledge or disregard
interlock 1 during override 2.
1704
INTLK2 OVR
1
0 = ACKNOWLEDGE
1 = DISREGARD
DISREGARD
(1)
Acknowledge or disregard
interlock 2 during override 2.
1706
INTLK4 OVR
1
0 = ACKNOWLEDGE
1 = DISREGARD
DISREGARD
(1)
Acknowledge or disregard
interlock 4 during override 2.
1707
FAULTS OVR
1
0 = ACKNOWLEDGE
1 = DISREGARD
DISREGARD
(1)
Acknowledge or disregard
overrideable bypass faults during
override 2.
All faults can be overridden
except:
3009, 3021, 3022, 3023, 3024,
3027, 3034, 3101, 3202, 3203,
3204, 3205, 3206
1708
OVRD2 MODE
1
1 = BYPASS
2 = VFD
3 = VFD/BYPASS
4 = STOP
BYPASS
(1)
1 = Use bypass contactor only
2 = Use drive only
3 = Use drive, switch to bypass
on drive fault
4 = Both contactors open
Group 16: System Control
Code
Name
Resolution
Range
Default
Description
Summary of Contents for ACH580 Series
Page 2: ......
Page 11: ...ACH580 BCR BDR VCR VDR E Clipse Bypass Drives 1 200 HP ...
Page 35: ...26 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 43: ...34 ACH580 E Clipse bypass and packaged drive user manual Start up ...
Page 67: ...58 ACH580 E Clipse bypass and packaged drive user manual Application macros ...
Page 193: ...184 ACH580 E Clipse bypass and packaged drive user manual Fieldbus adapter ...
Page 207: ...198 ACH580 E Clipse bypass and packaged drive user manual Diagnostics ...
Page 229: ...220 ACH580 E Clipse bypass and packaged drive user manual Technical data ...
Page 231: ...ACH580 PCR PDR Packaged Drives with Disconnect 1 200 HP ...
Page 243: ...234 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 256: ......