118
ACH580 E-Clipse bypass and packaged drive user manual
Embedded fieldbus
EFB Ref1/Ref2
Drive relay output control
Using the fieldbus for relay output control requires:
• Drive parameter values set as defined below.
• Only make these drive programming changes if you require control via BACnet.
• Fieldbus controller supplied, binary coded, relay command(s) in the appropriate
location.
Analog output control
Using the fieldbus for analog output control requires:
• Drive parameter values set as defined below.
• Fieldbus controller supplied analog value(s) in the appropriate location.
Drive Parameter
BACnet Access Point
19.11 Ext1/Ext2 Selection
BV13
3.09 EFB Ref1
AV16
3.10 EFB Ref2
AV17
Drive Parameter
Value
Setting
BACnet
Access Point
10.24 RO1
Source
RELAY OUTPUT 1 62, RO/DIO control
word
Relay Output 1
controlled by fieldbus.
BO0
10.27
RELAY OUTPUT 2 62, RO/DIO control
word
Relay Output 2
controlled by fieldbus.
BO1
10.30
RELAY OUTPUT 3 62, RO/DIO control
word
Relay Output 3
controlled by fieldbus.
BO2
15.07
1)
RELAY OUTPUT 4 62, RO/DIO control
word
Relay Output 4
controlled by fieldbus.
BO3
15.10
1)
RELAY OUTPUT 5 62, RO/DIO control
word
Relay Output 5
controlled by fieldbus.
BO4
15.23
1)
DO1 Source
DIGITAL OUTPUT
1
62, RO/DIO control
word
Digital Output 1
controlled by fieldbus.
BO5
1) More than 3 relays requires the addition of a relay extension module.
Drive Parameter
Value
Setting
BACnet
Access
Point
13.12
AO1 Source
37, AO1 Data
Storage
Analog Output 1 controlled by
writing to parameter 13.91.
–
13.91
AO1 Data Storage
–
AO0
13.22
AO2 Content Sel
38, AO2 Data
Storage
Analog Output 2 controlled by
writing to parameter 13.92.
–
13.92
AO2 Data Storage
–
AO1
Summary of Contents for ACH580 Series
Page 2: ......
Page 11: ...ACH580 BCR BDR VCR VDR E Clipse Bypass Drives 1 200 HP ...
Page 35: ...26 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 43: ...34 ACH580 E Clipse bypass and packaged drive user manual Start up ...
Page 67: ...58 ACH580 E Clipse bypass and packaged drive user manual Application macros ...
Page 193: ...184 ACH580 E Clipse bypass and packaged drive user manual Fieldbus adapter ...
Page 207: ...198 ACH580 E Clipse bypass and packaged drive user manual Diagnostics ...
Page 229: ...220 ACH580 E Clipse bypass and packaged drive user manual Technical data ...
Page 231: ...ACH580 PCR PDR Packaged Drives with Disconnect 1 200 HP ...
Page 243: ...234 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 256: ......