![background image](http://html.mh-extra.com/html/abb/ach580-series/ach580-series_user-manual_2512062.webp)
ACH580 E-Clipse bypass and packaged drive user manual
53
Application macros
Damper macro
Parameters Changed Relative to HVAC Default
*
Smoke Control (Override1) is a fixed input. Closing Digital Input 6
will
place the E-Clipse Bypass in Smoke
Control mode which may reassign the function of the other Digital Inputs. Refer to the Smoke Control
(Override1) documentation.
Parameter Number
Description
Setting
1602
Damper End Switch
PERMISSIVE
DI2
1604
Firestat, Freezestat, High Static Switch
INTERLOCK 2
DI4
Damper
Speed Reference / Process Setpoint
Process Feedback Signal
ACH580 CONTROL BOARD
E-CLIPSE BYPASS CONTROL BOARD
Terminal for Signal Cable Shield
Analog Input Common
Analog Input 2
10V / 10mA Reference Voltage for Potentiometer
Analog Input Common
Analog Input 1
X1
1
1
5
4
3
2
6
2
5
4
3
6
7
10
9
8
11
X2
25
23
22
21
20
24
19
18
17
16
15
14
13
12
+24VDC
+24VDC
Digital Input Common
GND
Digital Input 1
(Parameter 1601)
START/STOP
Digital Input 2
(Parameter 1602)
RUN PERMISSIVE
Digital Input 3
(Parameter 1603)
INTERLOCK 1
Digital Input 4
(Parameter 1604)
Digital Input 5
(Parameter 1605)
NOT SEL
Digital Input 5
(Fixed)
SMOKE CONTROL* (Override 1)
Relay Output 1
(Parameter 1401)
BYP NOT FLT
Default Operation: Bypass Not Faulted
11 connected to 13
Bypass Faulted 11 connected to 12
Relay Output 2
(Parameter 1404)
SYS RUNNING
Default Operation: System Running
14 connected to 16
Relay Output 3
(Parameter 1407)
SYS STARTED
Default Operation: System Started
17 connected to 19
Relay Output 4
(Parameter 1410)
BYPASS SEL
Default Operation: Bypass Selected
20 connected to 22
Relay Output 5
(Parameter 1413)
BYPASS AUTO
Default Operation: Bypass In Auto
23 connected to 25
Customer Auto Start
Firestat, Freezestat, High Static Switch
X2
Firestat, Freezestat, High Static Switch
Damper End Switch
To Damper Actuator
INTERLOCK 2
Summary of Contents for ACH580 Series
Page 2: ......
Page 11: ...ACH580 BCR BDR VCR VDR E Clipse Bypass Drives 1 200 HP ...
Page 35: ...26 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 43: ...34 ACH580 E Clipse bypass and packaged drive user manual Start up ...
Page 67: ...58 ACH580 E Clipse bypass and packaged drive user manual Application macros ...
Page 193: ...184 ACH580 E Clipse bypass and packaged drive user manual Fieldbus adapter ...
Page 207: ...198 ACH580 E Clipse bypass and packaged drive user manual Diagnostics ...
Page 229: ...220 ACH580 E Clipse bypass and packaged drive user manual Technical data ...
Page 231: ...ACH580 PCR PDR Packaged Drives with Disconnect 1 200 HP ...
Page 243: ...234 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 256: ......