ACH580 E-Clipse bypass and packaged drive user manual
205
Technical data
Branch circuit protection
Input power is connected to the ACH580 with E-Clipse Bypass through a door
interlocked disconnect switch or circuit breaker. Neither of these inputs are fused.
The branch circuit that provides power to the ACH580 with E-Clipse Bypass with
disconnect switch must include the specified external fuses to provide short circuit
and ground fault protection for the motor in the bypass mode.
When connected to a 240V or 480V power source, the ACH580 with E-Clipse
Bypass with the circuit breaker option is suitable for use on a circuit capable of
delivering not more than 100,000 RMS symmetrical amperes. When connected
to a 600V power source ABB E-Clipse units provided with a circuit breaker,
VCR and BCR configurations, are suitable for use on a circuit capable of
delivering not more than 10,000 RMS symmetrical amperes.
Fuses
Note:
The UL listed drive fuses in the table are provided in the purchased product.
• Replacement fuses are required to be of the same class, current rating, and
voltage rating. Fuses from other manufacturers can be used if they are 600V
rated and meet the specifications given in the table.
• Fuses with higher current rating than specified must not be used.
208/230 Volt fuses for vertical enclosures
Type Code
1
Nominal Output Ratings
Base
Drive
Frame
Size
Internal Drive
Fuse Rating
External Fuse for
Disconnect Option
Drive
Current
Package
Power
Class
Max
Current
Rating
Class
Max
Current
Rating
A
HP
208/230 Volts
ACH580-VxR-04A6-2
4.6
1
R1
Class CC
15A
Class J
15A
ACH580-VxR-06A6-2
6.6
1.5
R1
Class CC
15A
Class J
15A
ACH580-VxR-07A5-2
7.5
2
R1
Class CC
15A
Class J
20A
ACH580-VxR-10A6-2
10.6
3
R1
Class CC
15A
Class J
25A
ACH580-VxR-017A-2
16.7
5
R1
Class CC
30A
Class J
40A
ACH580-VxR-024A-2
24.2
7.5
R2
Class CC
30A
Class J
45A
ACH580-VxR-031A-2
30.8
10
R2
Class T
40A
Class J
60A
ACH580-VxR-046A-2
46.2
15
R3
Class T
80A
Class J
100A
ACH580-VxR-059A-2
59.4
20
R3
Class T
80A
Class J
100A
ACH580-VxR-075A-2
74.8
25
R4
Class T
100A
Class J
100A
1) “VxR” represents both VCR and VDR.
Summary of Contents for ACH580 Series
Page 2: ......
Page 11: ...ACH580 BCR BDR VCR VDR E Clipse Bypass Drives 1 200 HP ...
Page 35: ...26 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 43: ...34 ACH580 E Clipse bypass and packaged drive user manual Start up ...
Page 67: ...58 ACH580 E Clipse bypass and packaged drive user manual Application macros ...
Page 193: ...184 ACH580 E Clipse bypass and packaged drive user manual Fieldbus adapter ...
Page 207: ...198 ACH580 E Clipse bypass and packaged drive user manual Diagnostics ...
Page 229: ...220 ACH580 E Clipse bypass and packaged drive user manual Technical data ...
Page 231: ...ACH580 PCR PDR Packaged Drives with Disconnect 1 200 HP ...
Page 243: ...234 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 256: ......