ACH580 E-Clipse bypass and packaged drive user manual
129
Embedded fieldbus
Analog value object instance summary – Drive
The following table summarizes the Analog Value Objects supported:
Instance
ID
Object Name
Description
Units
Present Value
Access Type
AV0
OUTPUT
SPEED
This object indicates the calculated motor
speed in RPM. The corresponding drive
parameter is 01.01.
RPM
R
AV1
OUTPUT FREQ This object indicates the output
frequency applied to the motor in Hz. The
corresponding drive parameter is 01.06.
Hertz
R
AV2
DC BUS VOLT
This object indicates the drive’s DC bus
voltage level. The corresponding drive
parameter is 01.11.
Volts
R
AV3
OUTPUT VOLT
This object indicates the AC output
voltage applied to the motor. The
corresponding drive parameter is 01.13.
Volts
R
AV4
CURRENT
This object indicates the measured
output current. The corresponding drive
parameter is 01.07.
Amps
R
AV5
TORQUE
This object indicates the calculated motor
output torque as a percentage of nominal
torque. The corresponding drive
parameter is 01.10.
Percent
R
AV6
POWER
This object indicates the measured
output power in kW. The corresponding
drive parameter is 01.14.
Kilowatts
R
AV7
DRIVE TEMP
This object indicates the measured
heatsink temperature expressed as
percent where:
0% = 0°C (32°F)
100% = Fault limit
The corresponding drive parameter is
05.11
Percent
R
AV8
KWH (R)
This object indicates, in kW hours, the
drive’s accumulated energy usage since
the last reset. The value can be reset to
zero. The corresponding drive parameter
is 01.58.
kWh
W
AV9
KWH (NR)
This object indicates the drive’s
accumulated energy usage in MW hours.
The value cannot be reset.
MWh
R
AV10
PRC PID FBCK This object is the Process PID feedback
signal. The corresponding drive
parameter is 40.97.
Percent
R
AV11
PRC PID DEV
This object is the Process PID output
signal’s deviation from its setpoint. The
corresponding drive parameter is 40.99.
Percent
R
AV12
EXT PID FBCK
This object is the External PID feedback
signal. Calculated as (drive parameter
71.02) / drive parameter 71.14).
Percent
R
Summary of Contents for ACH580 Series
Page 2: ......
Page 11: ...ACH580 BCR BDR VCR VDR E Clipse Bypass Drives 1 200 HP ...
Page 35: ...26 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 43: ...34 ACH580 E Clipse bypass and packaged drive user manual Start up ...
Page 67: ...58 ACH580 E Clipse bypass and packaged drive user manual Application macros ...
Page 193: ...184 ACH580 E Clipse bypass and packaged drive user manual Fieldbus adapter ...
Page 207: ...198 ACH580 E Clipse bypass and packaged drive user manual Diagnostics ...
Page 229: ...220 ACH580 E Clipse bypass and packaged drive user manual Technical data ...
Page 231: ...ACH580 PCR PDR Packaged Drives with Disconnect 1 200 HP ...
Page 243: ...234 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 256: ......