ACH580 E-Clipse bypass and packaged drive user manual
Embedded fieldbus
consume two nodes on a N2 fieldbus segment, if both the drive and bypass objects
are being polled by the system.
Drive device type
For the Metasys and Metasys Companion products, the device type for the ACH580
drive is VND.
When bypass parameter 1625 COMM CTL= (0) DRIVE ONLY, drive’s N2 objects are
all supported using the drive’s device address. The bypass’s N2 objects related to
the control word are no longer valid. For further information on the functional
implications of the setting of parameter 1625, see
on
page
.
Bypass N2 Objects Not Valid
When bypass parameter 1625 COMM CTL= (1) SYSTEM, drive’s N2 following
objects related to control are no longer available when using the drive’s device
address.
Drive N2 Objects Not Valid
Drive Overview
The ACH580 drive does not support N2 Fieldbus communication “internal values”.
All of the Analog and Binary I/O objects are listed below.
Analog Input
– The analog input objects support the following features:
• Analog Input actual value in engineering units
• Low Warning limit
• Low Warning limit
• High Warning limit
• High Warning limit
• Differential value for the hysteresis of the Alarms and Warnings
Number
Object
Bypass Parmeter
BO1
SYSTEM START
Command Word
BO2
SYSTEM DISABLE
Command Word
BO3
SYSTEM RESET
Command Word
BO4
OVERRIDE
Command Word
B10
START INTERLOCK 1
Command Word
B11
START INTERLOCK 2
Command Word
B12
START INTERLOCK 3
Command Word
B13
START INTERLOCK 4
Command Word
Number
Object
Bypass Parameter
BO1
START/STOP
Command Word
BO2
RUN PERMISSIVE
Command Word
BO3
N2 LOCAL CTL
Command Word
Summary of Contents for ACH580 Series
Page 2: ......
Page 11: ...ACH580 BCR BDR VCR VDR E Clipse Bypass Drives 1 200 HP ...
Page 35: ...26 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 43: ...34 ACH580 E Clipse bypass and packaged drive user manual Start up ...
Page 67: ...58 ACH580 E Clipse bypass and packaged drive user manual Application macros ...
Page 193: ...184 ACH580 E Clipse bypass and packaged drive user manual Fieldbus adapter ...
Page 207: ...198 ACH580 E Clipse bypass and packaged drive user manual Diagnostics ...
Page 229: ...220 ACH580 E Clipse bypass and packaged drive user manual Technical data ...
Page 231: ...ACH580 PCR PDR Packaged Drives with Disconnect 1 200 HP ...
Page 243: ...234 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 256: ......