76
ACH580 E-Clipse bypass and packaged drive user manual
Embedded fieldbus
Control interface
In general, the basic control interface between the fieldbus system and the drive
consists of:
Note:
The words “output” and “input” are used as seen from the fieldbus controller
point of view. For example an output describes data flow from the fieldbus controller
to the bypass.
Mechanical and electrical installation – Embedded Fieldbus (EFB)
Warning!
Connections should be made only while the bypass is disconnected from
the power source.
Bypass terminals 26…30 are for EIA 485 communications.
• Use Belden 9842 or equivalent. Belden 9842 is a dual twisted, shielded pair cable
with a wave impedance of 120
Ω
.
• Use one of these twisted shielded pairs for the EIA 485 link. Use this pair to
connect all A (-) terminals together and all B (+) terminals together.
• Use both of the other wires in the other pair for the reference/common
(terminal 29).
Protocol
Control Interface
Reference for more information
Modbus
• Output Words
– Control word
– Reference1
– Reference2
• Input Words
– Status word
– Actual value 1
– Actual value 2
– Actual value 3
– Actual value 4
– Actual value 5
– Actual value 6
– Actual value 7
– Actual value 8
The content of these words is defined by profiles. For
details on the profiles used, see
starting on page
N2
• Binary output objects
• Analog output objects
• Binary input objects
• Analog input objects
N2 protocol technical data – system
on page
and
on page
BACnet
• Device management
• Binary output objects
• Analog output objects
• Binary input objects
• Analog input objects
BACnet protocol technical data – system
on page
Summary of Contents for ACH580 Series
Page 2: ......
Page 11: ...ACH580 BCR BDR VCR VDR E Clipse Bypass Drives 1 200 HP ...
Page 35: ...26 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 43: ...34 ACH580 E Clipse bypass and packaged drive user manual Start up ...
Page 67: ...58 ACH580 E Clipse bypass and packaged drive user manual Application macros ...
Page 193: ...184 ACH580 E Clipse bypass and packaged drive user manual Fieldbus adapter ...
Page 207: ...198 ACH580 E Clipse bypass and packaged drive user manual Diagnostics ...
Page 229: ...220 ACH580 E Clipse bypass and packaged drive user manual Technical data ...
Page 231: ...ACH580 PCR PDR Packaged Drives with Disconnect 1 200 HP ...
Page 243: ...234 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 256: ......