28
ACH580 E-Clipse bypass and packaged drive user manual
Control panel
Bypass Faulted LED
The
Bypass Faulted LED
is illuminated or flashes red when the motor or bypass
protection functions have shut down the bypass. The specific nature of the fault is
indicated on the bypass control display. Refer to the
section on
page
for more details.
Drive Selected LED
The
Drive Selected LED
is illuminated green when the drive has been selected as
the power source for the motor and no drive fault is present.
Bypass Selected LED
The
Bypass Selected LED
is illuminated or flashes green when the bypass has been
selected as the power source for the motor and no bypass fault is present.
Drive Faulted LED
The
Drive Faulted LED
is illuminated red when the bypass has lost its
communications link with the drive or when the motor or drive protection functions
have shut down the drive. The specific nature of the fault is indicated on the drive
control panel display. Refer to the
section on page
for more details.
Automatic Transfer
The
Automatic Transfer
indication is provided on the bypass control panel. The
bypass control display will continuously flash an warning to indicate the system has
automatically transferred to Bypass after a Drive fault. The Bypass Selected LED
flashes green when the system has automatically transferred to bypass operation.
The bypass event log will also record this event.
Auto Indication
The
Auto Indication
is provided on the bypass control panel default display when the
bypass control panel Auto key is pressed. Normally this indicates that the Auto Start
contact or communications has been selected as the means for starting and
stopping the motor in the bypass mode.
Off Indication
The
Off Indication
is provided on the bypass control panel default display when
bypass control panel Off key is pressed.
Hand Indication
The
Hand Indication
is provided on the bypass control panel default display when
the motor has been started manually in the bypass mode.
Drive Select Key
The
Drive Select Key
selects the drive as the power source for the motor.
Bypass Select Key
The
Bypass Select Key
selects the bypass as the power source for the motor.
Off/Reset Key
The
Off/Reset Key
may be used to manually stop the motor if the motor has been
running on bypass power. The Off/Reset key also resets most bypass faults. It may
Summary of Contents for ACH580 Series
Page 2: ......
Page 11: ...ACH580 BCR BDR VCR VDR E Clipse Bypass Drives 1 200 HP ...
Page 35: ...26 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 43: ...34 ACH580 E Clipse bypass and packaged drive user manual Start up ...
Page 67: ...58 ACH580 E Clipse bypass and packaged drive user manual Application macros ...
Page 193: ...184 ACH580 E Clipse bypass and packaged drive user manual Fieldbus adapter ...
Page 207: ...198 ACH580 E Clipse bypass and packaged drive user manual Diagnostics ...
Page 229: ...220 ACH580 E Clipse bypass and packaged drive user manual Technical data ...
Page 231: ...ACH580 PCR PDR Packaged Drives with Disconnect 1 200 HP ...
Page 243: ...234 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 256: ......