72
ACH580 E-Clipse bypass and packaged drive user manual
Parameters
5807
DV STATUS
1
0=IDLE,
1=EXECUT INIT,
2=TIME OUT,
3=CONFIG ERR,
4=OFF-LINE,
5=ON-LINE,
6=RESET,
7=LISTEN ONLY
0
Contains the status of the drive
EFB protocol.
5808
DV OK MSG
1
0 - 65535
0
Contains a count of valid
messages received by the drive.
• During normal operation, this
counter is increasing
constantly.
5811
UART ERROR
1
0 - 65535
0
Contains a count of the messages
with a character error received by
the drive.
5812
DV CRC ERR
1
0 - 65535
0
Contains a count of the messages
with a CRC error received by the
drive.
5813
TOKEN CNT
1
0 - 65535
0
Contains a count of the number of
times the drive has received the
token.
5817
TX DELAY
1
0 - 65535
0
Defines the drive minimum
response delay in addition to any
fixed delay imposed by the
protocol.
5818
EFB CNTRL
1
0 - 0xFFFF
0
Displays the raw (unmodified)
control word sent by the Modbus
controller to the drive. This
parameter is read-only.
5819
EFB STAT
1
0 - 0xFFFF
0
Status word sent by the drive to
the Modbus controller. this
parameter is read-only.
5825
PROFILE
1
0=ABB DRV LIM,
1=DCU PROFILE,
2=ABB DRV FULL
0
Selects the communications
profile used by the EFB protocol.
5840
DV OB ID L
1
0 - 65535
4303
BACnet Device object ID lower
word.
The Drive’s Device object ID must
be unique across all BACnet
devices in the building network.
Valid values are 0…4194303. The
Device Object ID is formed as a
combination of parameter 5840
and 5899. To set an ID from 1 to
65535 set this parameter = to the
desired ID and set 5899 = 0. To
set an ID greater than 65535, set
this parameter to the lower 4 digits
of the ID and set 5899 to the
remaining upper digits. For
example, to set the ID to 71234,
set the 5840 = 1234 and 5899 = 7.
The default values of 5840 = 0
and 5899 = 0 are handled
specially. This case uses
parameter 5803, the MAC ID as
the value for the device object ID.
5841
MAX MASTER
1
0 - 127
127
The Drive’s highest master
address for devices on the
BACnet MS/TP bus.
5842
MAX INF FR
1
0 - 10
1
The maximum number of
information frames the drive may
transmit before it must pass the
token.
5899
DV OB ID H
1
0 - 419
419
BACnet Device object ID upper
word. See parameter 58.40 for
description of how to use this
parameter.
58100
DB REV
1
0 - 65535
0
BACnet Database Revision
Group 58: Drive EFB
Code
Name
Resolution
Range
Default
Description
Summary of Contents for ACH580 Series
Page 2: ......
Page 11: ...ACH580 BCR BDR VCR VDR E Clipse Bypass Drives 1 200 HP ...
Page 35: ...26 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 43: ...34 ACH580 E Clipse bypass and packaged drive user manual Start up ...
Page 67: ...58 ACH580 E Clipse bypass and packaged drive user manual Application macros ...
Page 193: ...184 ACH580 E Clipse bypass and packaged drive user manual Fieldbus adapter ...
Page 207: ...198 ACH580 E Clipse bypass and packaged drive user manual Diagnostics ...
Page 229: ...220 ACH580 E Clipse bypass and packaged drive user manual Technical data ...
Page 231: ...ACH580 PCR PDR Packaged Drives with Disconnect 1 200 HP ...
Page 243: ...234 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 256: ......