![background image](http://html.mh-extra.com/html/abb/ach580-series/ach580-series_user-manual_2512079.webp)
70
ACH580 E-Clipse bypass and packaged drive user manual
Parameters
Group 51: External Comm Mode
Group 52: FBA Data In
Group 51: External Comm Mode
Code
Name
Resolution
Range
Default
Description
5101
FBA TYPE
1
0 = NOT DEFINED
1 = Profibus
15 = LonWorks
37 = DeviceNet
502 = Modbus TCP
2222 Ethernet/IP
—
Displays type of attached
fieldbus adapter module.
5102
...
5126
FBA PAR 2
...
FBA PAR 26
1
0 - 65535
0
Fieldbus specific - consult FBA
User’s Manual.
5127
REFRESH
1
0 = DONE
1 = REFRESH
0
Validates any changed adapter
module configuration
parameters. After refreshing,
value reverts automatically to
DONE.
5128
FBA PAR 28
1
0 - 0xFFFF
0
Parameter table version
5129
FBA PAR 29
1
0 - 0xFFFF
0
Bypass type code
5130
FBA PAR 30
1
0 - 0xFFFF
0
Mapping file version
5131
FBA PAR 31
1
0 - 6
0
Fieldbus adapter status
5132
FBA PAR 32
1
0 - 0xFFFF
0
Module common software
version
5133
FBA PAR 33
0 - 0xFFFF
0
Module application software
version
Group 52: FBA Data In
Code
Name
Resolution
Range
Default
Description
5201
...
5210
DATA IN 1
...
DATA IN 10
1
0 = Not In Use
1 = Control Word (ABBDP)
2 = Ref 1 (ABBDP)
3 = Ref 2 (ABBDP)
4 = Status Word (ABBDP)
5 = Actual Value 1 (ABBDP)
6 = Actual Value 2 (ABBDP)
0101h -063FFh = Drive
parameters
8101h - E3FFh = Bypass
para 8000h
0
Specifies information to be
read from the drive (into
the network). Only for
modules that support the
cyclic low scanner function
(such as FMBT-12).
For specifying values 1-6,
select ABB drive’s profile
information, like status
word or actual values.
To specify drive
parameters, use the format
ggh.pph where gg
h
is the
parameter group in
hexadecimal and pp
h
is
the parameter in
hexadecimal.
For instance, drive
parameter 30.14 is
encoded as 1E0Eh.
Bypass parameter is
specified as 8000h +
gg
h
.pp
h
. For instance,
bypass parameter 0114 is
encoded as 810Eh.
Summary of Contents for ACH580 Series
Page 2: ......
Page 11: ...ACH580 BCR BDR VCR VDR E Clipse Bypass Drives 1 200 HP ...
Page 35: ...26 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 43: ...34 ACH580 E Clipse bypass and packaged drive user manual Start up ...
Page 67: ...58 ACH580 E Clipse bypass and packaged drive user manual Application macros ...
Page 193: ...184 ACH580 E Clipse bypass and packaged drive user manual Fieldbus adapter ...
Page 207: ...198 ACH580 E Clipse bypass and packaged drive user manual Diagnostics ...
Page 229: ...220 ACH580 E Clipse bypass and packaged drive user manual Technical data ...
Page 231: ...ACH580 PCR PDR Packaged Drives with Disconnect 1 200 HP ...
Page 243: ...234 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 256: ......