190
ACH580 E-Clipse bypass and packaged drive user manual
Diagnostics
3038
NO DRIVE
DATA
No drive data available
(Group 112)
Bypass not able to
extract drive data on
initial power up due
to:
Bad cable/
connection between
drive and bypass.
Drive parameter
95.21, bit 5 not set
for Bypass present.
Proper seating of cable in
drive and RBCU
(connector J3).
Check that drive parameter
95.21, bit 5 is set.
3039
FBA PAR
CONF
Non embedded fieldbus
has detected an error in
Group 51 parameters
Incorrect settings in
Group 51
Verify Group 51 parameters
3101
SFLASH
CORRUPT
Internal checksum error N/A
Cycle power
Replace RBCU
Upgrade firmware
3102
PMAP FILE
Parameter file is corrupt
Cycle Power
Contact ABB with information
that preceded fault
3201
T1
OVERLOAD
T1 program cycle is
overloaded
N/A
Contact ABB with information
that preceded fault
Cycle Power
Replace RBCU
3202
T2
OVERLOAD
T2 program cycle is
overloaded
N/A
Contact ABB with information
that preceded fault
Cycle Power
Replace RBCU
3203
T3
OVERLOAD
T3 program cycle is
overloaded
N/A
Contact ABB with information
that preceded fault
Cycle Power
Replace RBCU
3204
STACK
OVERFLOW
Program cycle is
overloaded
N/A
Contact ABB with information
that preceded fault
Cycle Power
Replace RBCU
3205
UNKNOWN
CB
Bypass control board
type is unknown.
Firmware is not
compatible with
control board in
RBCU.
Contact ABB at
1-800-752-0696 option 1
3206
UNKNOWN
DRIVE
Drive reports rating not
found in bypass
software
Drive does not match
drives configured in
bypass RBCU
Replace RBCU or reload with
most current firmware
3207
UNKNOWN
BYPASS
N/A
N/A
Replace RBCU or load most
current firmware
Contact ABB at
1-800-752-0696 option 1
Replace RBCU or load most
current firmware
Fault
Code
Fault Name
In Panel
Fault
Possible Cause
Corrective Action
Summary of Contents for ACH580 Series
Page 2: ......
Page 11: ...ACH580 BCR BDR VCR VDR E Clipse Bypass Drives 1 200 HP ...
Page 35: ...26 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 43: ...34 ACH580 E Clipse bypass and packaged drive user manual Start up ...
Page 67: ...58 ACH580 E Clipse bypass and packaged drive user manual Application macros ...
Page 193: ...184 ACH580 E Clipse bypass and packaged drive user manual Fieldbus adapter ...
Page 207: ...198 ACH580 E Clipse bypass and packaged drive user manual Diagnostics ...
Page 229: ...220 ACH580 E Clipse bypass and packaged drive user manual Technical data ...
Page 231: ...ACH580 PCR PDR Packaged Drives with Disconnect 1 200 HP ...
Page 243: ...234 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 256: ......