N2 binary output objects – Drive
The following table lists the N2 Binary Output objects defined for the ACH580 drive.
N2 Binary Outputs:
Number
Object
Drive Parameter
Range
BO1
STOP/START
Command Word
0 = Stop, 1 = Start to Speed
BO2
FORWARD/REVERSE
Command Word
0 = Forward, 1 = Reverse
BO3
PANEL LOCK
Command Word
0 = Open, 1 = Locked
BO4
RUN PERMISSIVE
Command Word
0 = Enable, 1 = Disable
BO5
REF1/REF2 SELECT
Command Word
0 = Ref1, 1 = Ref2
BO6
FAULT RESET
Command Word
Change 0 -> 1 Resets
BO7
COMMAND RO 1
10.99, bit0
0 = Off, 1 = On
BO8
COMMAND RO 2
10.99, bit1
0 = Off, 1 = On
BO9
COMMAND RO 3
10.99, bit2
0 = Off, 1 = On
BO10
COMMAND RO 4
10.99, bit3
0 = Off, 1 = On
BO11
COMMAND RO 5
10.99, bit4
0 = Off, 1 = On
BO12
COMMAND RO 6
10.99, bit5
0 = Off, 1 = On
BO13
RESET RUN TIME
Indirectly mapping
0 = N/A, 1 = On (Reset Run Time)
BO14
RESET KWH COUNT
Indirectly mapping
0 = N/A, 1 = On (Reset kWh Count)
BO15
PRC PID SELECT
40.57 (indirectly)
0 = SET2, 1 = SET2
BO16
N2 LOCAL CTL (Note 1)
DCU Control Word,
BIT16
0 = Auto, 1 = N2
BO17
N2 LOCAL REF (Note 1)
DCU Control Word,
BIT17
0 = Auto, 1 = N2
BO18
SAVE PARAMETERS
96.07 (indirectly)
0 = N/A, 1 = On (Save Parameters)
BO19
READ MB
N/A
0 = NO, 1 = READ
BO20
WRITE MB
N/A
0 = NO, 1 = WRITE
1) N2 LOCAL CTL and N2 LOCAL REF have priority over drive input terminals. Use these binary
outputs for temporary N2 control of the drive when
COMM
is not the selected control source.
Summary of Contents for ACH580 Series
Page 2: ......
Page 11: ...ACH580 BCR BDR VCR VDR E Clipse Bypass Drives 1 200 HP ...
Page 35: ...26 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 43: ...34 ACH580 E Clipse bypass and packaged drive user manual Start up ...
Page 67: ...58 ACH580 E Clipse bypass and packaged drive user manual Application macros ...
Page 193: ...184 ACH580 E Clipse bypass and packaged drive user manual Fieldbus adapter ...
Page 207: ...198 ACH580 E Clipse bypass and packaged drive user manual Diagnostics ...
Page 229: ...220 ACH580 E Clipse bypass and packaged drive user manual Technical data ...
Page 231: ...ACH580 PCR PDR Packaged Drives with Disconnect 1 200 HP ...
Page 243: ...234 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 256: ......