![background image](http://html.mh-extra.com/html/abb/ach580-series/ach580-series_user-manual_2512143.webp)
134
ACH580 E-Clipse bypass and packaged drive user manual
Embedded fieldbus
BACnet input object instance summary – Bypass
The following table summarizes the Binary Input Objects supported:
Note:
For Present Value Access Types, R = Read-only, W = Writeable,
C = Commandable. Commandable values support priority arrays and relinquish
defaults.
BACnet output object instance summary – Bypass
The following table summarizes the Binary Output Objects supported:
Instance
ID
Object
Name
Description
Active/
Inactive Text
Present Value
Access Type
BI0
RO 1 ACT
This object indicates the status of
bypass Relay Output 1.
ON/OFF
R
BI1
RO 2 ACT
This object indicates the status of
bypass Relay Output 2.
ON/OFF
R
BI2
RO 3 ACT
This object indicates the status of
bypass Relay Output 3.
ON/OFF
R
BI3
RO 4 ACT
This object indicates the status of
bypass Relay Output 4.
ON/OFF
R
BI4
RO 5 ACT
This object indicates the status of
bypass Relay Output 5.
ON/OFF
R
BI5
DI 1 ACT
This object indicates the status of
bypass Digital Input 1.
ON/OFF
R
BI6
DI 2 ACT
This object indicates the status of
bypass Digital Input 2.
ON/OFF
R
BI7
DI 3 ACT
This object indicates the status of
bypass Digital Input 3.
ON/OFF
R
BI8
DI 4 ACT
This object indicates the status of
bypass Digital Input 4.
ON/OFF
R
BI9
DI 5 ACT
This object indicates the status of
bypass Digital Input 5.
ON/OFF
R
BI10
DI 6 ACT
This object indicates the status of
bypass Digital Input 6.
ON/OFF
R
Instance
ID
Object Name
Description
Active/
Inactive Text
Present Value
Access Type
BO0
RO1 COMMAND This object controls the output state
of bypass Relay Output 1. This
control requires that parameter
1401 value =
COMM
.
ON/OFF
C
BO1
RO2 COMMAND This object controls the output state
of bypass Relay Output 2. This
control requires that parameter
1404 value =
COMM
.
ON/OFF
C
BO2
RO3 COMMAND This object controls the output state
of bypass Relay Output 3. This
control requires that parameter
1407 value =
COMM
.
ON/OFF
C
Summary of Contents for ACH580 Series
Page 2: ......
Page 11: ...ACH580 BCR BDR VCR VDR E Clipse Bypass Drives 1 200 HP ...
Page 35: ...26 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 43: ...34 ACH580 E Clipse bypass and packaged drive user manual Start up ...
Page 67: ...58 ACH580 E Clipse bypass and packaged drive user manual Application macros ...
Page 193: ...184 ACH580 E Clipse bypass and packaged drive user manual Fieldbus adapter ...
Page 207: ...198 ACH580 E Clipse bypass and packaged drive user manual Diagnostics ...
Page 229: ...220 ACH580 E Clipse bypass and packaged drive user manual Technical data ...
Page 231: ...ACH580 PCR PDR Packaged Drives with Disconnect 1 200 HP ...
Page 243: ...234 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 256: ......