ACH580 E-Clipse bypass and packaged drive user manual
85
Embedded fieldbus
Note:
After any changes to the communication settings, the communication channel
must be reset by either cycling the system power, or by clearing (set to 0 and enter)
and then restoring the station ID (5002) to desired station ID.
Activate drive control functions – EFB
Controlling the drive
Fieldbus control of various drive functions requires configuration to:
• Tell the drive (via the bypass) to accept fieldbus control of the function.
• Define as a fieldbus input, any drive data required for control.
• Define as a fieldbus output, any control data required by the drive.
The following sections describe, at a general level, the configuration required for
each control function. For the protocol-specific details, see the specific protocol
technical data section in this manual.
Start/stop control (Drive only)
Using the fieldbus for start/stop control of the drive only requires:
• Bypass parameter values set as defined below.
• Fieldbus controller supplied command(s) in the appropriate location. (The
location is defined by the Protocol Reference, which is protocol dependent.)
• Control commands must be addressed to the Drive node with parameter 1625 set
to 0 (
DRIVE ONLY
). For SYSTEM control refer to
page
5099
BY OB ID H
BACnet Device object ID upper
word. See parameter 5040 for
description of how to use this
parameter.
N/A
N/A
Resolution: 1
Range: 0-419
Default: 0
Bypass
Parameter
Value
Description
Protocol Reference
Modbus
1
N2
BACnet
ABB DRV
DCU
PROFILE
1601 START/
STOP
2 (COMM)
Start/Stop by
fieldbus with Ext1
or Ext2 selected.
40001 bits
0…3 (see
page
)
40031 bits
0, 1 (see
page
BO1 BV10
1625 COMM
CTRL
0 (DRIVE
ONLY)
Enable drive only
control.
N/A
1) For Modbus, the protocol reference can depend on the profile used, hence two columns in
these tables. One column refers to the ABB Drives profile, selected when parameter 5825 = 0
(ABB DRV LIM) or 5825 = 2 (ABB DRV FULL). The other column refers to the DCU profile
selected when parameter 5825 = 1 (DCU PROFILE). See
ABB control profiles technical data –
section on page
Bypass
Parameter
Description
EFB Protocol Reference
Modbus
N2
BACnet
Summary of Contents for ACH580 Series
Page 2: ......
Page 11: ...ACH580 BCR BDR VCR VDR E Clipse Bypass Drives 1 200 HP ...
Page 35: ...26 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 43: ...34 ACH580 E Clipse bypass and packaged drive user manual Start up ...
Page 67: ...58 ACH580 E Clipse bypass and packaged drive user manual Application macros ...
Page 193: ...184 ACH580 E Clipse bypass and packaged drive user manual Fieldbus adapter ...
Page 207: ...198 ACH580 E Clipse bypass and packaged drive user manual Diagnostics ...
Page 229: ...220 ACH580 E Clipse bypass and packaged drive user manual Technical data ...
Page 231: ...ACH580 PCR PDR Packaged Drives with Disconnect 1 200 HP ...
Page 243: ...234 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 256: ......