ACH580 E-Clipse bypass and packaged drive user manual
115
Embedded fieldbus
Quick-start sequence - drive communications
The following steps summarize the process for enabling and configuring BACnet on
the ABB E-Clipse Bypass:
1. Enable BACnet protocol: Set bypass parameter 9802, COMM PROTOCOL SEL
BACNET (5).
• To confirm this selection, read bypass parameter 5803, EFB PROTOCOL ID. It
should read x5xx (where “x” is any value).
2. Place the BACnet channel in “reset”: Set bypass parameter 5803, EFB STATION
ID = 0.
• This setting holds the BACnet communication channel in reset while remaining
settings are completed.
3. Define the MS/TP baud rate.
• Set bypass parameter 5803, EFB BAUD RATE = appropriate value
4. Define the Device Object instance.
• To define a specific device object instance value, use bypass parameters 5840
and 5899 (object instance values must be unique and in the range 0
to 4,194,302).
• To use the bypass’ MS/TP MAC ID as the device object instance value, set
bypass parameter 5840 and 5899 = 0.
• BACnet requires a unique Device Object ID for each device on the BACnet
network.
5. Define a unique MS/TP MAC ID. Set bypass parameter 5802, EFB STATION ID =
appropriate value.
• Once this parameter is set to a non-zero value, current BACnet settings are
“latched” and used for communication until the channel is reset.
• In order to participate in MS/TP token passing, the MAC ID used must be within
the limits defined by other masters’ “Max Master” property.
6. Confirm proper BACnet communication.
• When BACnet communication is operating properly, bypass parameter 5813,
EFB PAR 16 (the MS/TP token counter), should be continually increasing.
• Bypass parameter 5811, UART ERRORS, should be stable.
7. Configure the Device Object Name.
• BACnet requires a unique name for each device on the BACnet network. Write
the Object Name of the Device Object of the drive to a unique text string using the
operator workstation or software tool capable of writing BACnet properties. The
Object Name cannot be modified with the ABB display panel and only the Device
object name is writable in this product. The E-Clipse bypass does not support
writing of Device Description.
Summary of Contents for ACH580 Series
Page 2: ......
Page 11: ...ACH580 BCR BDR VCR VDR E Clipse Bypass Drives 1 200 HP ...
Page 35: ...26 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 43: ...34 ACH580 E Clipse bypass and packaged drive user manual Start up ...
Page 67: ...58 ACH580 E Clipse bypass and packaged drive user manual Application macros ...
Page 193: ...184 ACH580 E Clipse bypass and packaged drive user manual Fieldbus adapter ...
Page 207: ...198 ACH580 E Clipse bypass and packaged drive user manual Diagnostics ...
Page 229: ...220 ACH580 E Clipse bypass and packaged drive user manual Technical data ...
Page 231: ...ACH580 PCR PDR Packaged Drives with Disconnect 1 200 HP ...
Page 243: ...234 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 256: ......