140
ACH580 E-Clipse bypass and packaged drive user manual
Embedded fieldbus
• Bit-wise map of the CONTROL WORD (selected using bypass parameter 5825
EFB CTRL PROFILE). The first 32 coils are reserved for this purpose.
• Relay output states, numbered sequentially beginning with coil 00033.
The following table summarizes the 0xxxx reference set:
For the 0xxxx registers:
• Status is always readable.
• Forcing is allowed by user configuration of the drive for fieldbus control.
• Additional relay outputs are added sequentially.
Modbus
Ref.
Internal Location
(All Profiles)
ABB DRV LIM
BP Param
(5825 = 0)
DCU PROFILE
BP Param
(5825 = 1)
ABB DRV FULL
BP Param
(5825 = 2)
0
0001
CONTROL WORD – Bit 0
OFF1
1
STOP
OFF1*
0
0002
CONTROL WORD – Bit 1
OFF2
1
START
OFF2*
0
0003
CONTROL WORD – Bit 2
OFF3
1
REVERSE
OFF3*
0
0004
CONTROL WORD – Bit 3
START
N/A
START
0
0005
CONTROL WORD – Bit 4
N/A
RESET
RAMP_OUT_ZERO*
0
0006
CONTROL WORD – Bit 5
RAMP_HOLD*
EXT2
RAMP_HOLD*
0
0007
CONTROL WORD– Bit 6
RAMP_IN_ZERO*
RUN_DISABLE
RAMP_IN_ZERO*
0
0008
CONTROL WORD – Bit 7
RESET
STPMODE_R
RESET
0
0009
CONTROL WORD – Bit 8
N/A
STPMODE_EM
N/A
0
0010
CONTROL WORD – Bit 9
N/A
STPMODE_C
N/A
0
0011
CONTROL WORD – Bit 10
N/A
RAMP_2
REMOTE_CMD*
0
0012
CONTROL WORD – Bit 11
EXT2
RAMP_OUT_0
EXT2
0
0013
CONTROL WORD – Bit 12
N/A
RAMP_HOLD
N/A
0
0014
CONTROL WORD – Bit 13
N/A
RAMP_IN_0
N/A
0
0015
CONTROL WORD – Bit 14
N/A
REQ_LOCALLOCK
N/A
0
0016
CONTROL WORD – Bit 15
N/A
TORQLIM2
N/A
0
0017
CONTROL WORD – Bit 16
Does not apply
FBLOCAL_CTL
Does not apply
0
0018
CONTROL WORD – Bit 17
FBLOCAL_REF
0
0019
CONTROL WORD – Bit 18
START_DISABLE1
0
0020
CONTROL WORD – Bit 19
START_DISABLE2
0
0021…
0
0032
Reserved
Reserved
Reserved
Reserved
0
0033
RELAY OUTPUT 1
Relay Output 1
Relay Output 1
Relay Output 1
0
0034
RELAY OUTPUT 2
Relay Output 2
Relay Output 2
Relay Output 2
0
0035
RELAY OUTPUT 3
Relay Output 3
Relay Output 3
Relay Output 3
0
0036
RELAY OUTPUT 4
Relay Output 4
Relay Output 4
Relay Output 4
0
0037
RELAY OUTPUT 5
Relay Output 5
Relay Output 5
Relay Output 5
0
0038
RELAY OUTPUT 6
Relay Output 6
Relay Output 6
Relay Output 6
1) = Active low
Summary of Contents for ACH580 Series
Page 2: ......
Page 11: ...ACH580 BCR BDR VCR VDR E Clipse Bypass Drives 1 200 HP ...
Page 35: ...26 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 43: ...34 ACH580 E Clipse bypass and packaged drive user manual Start up ...
Page 67: ...58 ACH580 E Clipse bypass and packaged drive user manual Application macros ...
Page 193: ...184 ACH580 E Clipse bypass and packaged drive user manual Fieldbus adapter ...
Page 207: ...198 ACH580 E Clipse bypass and packaged drive user manual Diagnostics ...
Page 229: ...220 ACH580 E Clipse bypass and packaged drive user manual Technical data ...
Page 231: ...ACH580 PCR PDR Packaged Drives with Disconnect 1 200 HP ...
Page 243: ...234 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 256: ......