ACH580 E-Clipse bypass and packaged drive user manual
Parameters
Note:
For wiring requirements and additional configuration detail refer to
on page
.
Group 30: Fault Function
Group 32: Supervisory Control
Group 33: Information
Group 30: Fault Function
Code
Name
Resolution
Range
Default
Description
3001
UL ACTION
1
0 = NOT SEL
1 = FAULT
2 = WARNING
NOT SEL
(0)
Selects action to be taken if
underload occurs.
3002
UL TIME
1 sec
10 - 400 sec
20 sec
Time below underload level
before fault is declared.
3003
UL TRIP %
1%
0 - 100%
20%
Sets power level at which
underload is declared.
3004
COMM LOSS
1
0 = NOT SEL
1 = FAULT
2 = CONST SP7
3 = LAST SPEED
NOT SEL
(0)
This parameter serves similar
purpose as parameter 58.14 in
drive which specifies behavior if
communication link goes down.
3005
COMM TIME
0.1s
0.0 - 600.0s
0
Sets the communication fault
time used with COMM LOSS
parameter. A value of “0”
disables the timer.
3006
PHASE LOSS
1
0 = DISABLE
1 = ENABLE
1
Provides input phase loss
detection for bypass mode.
3007
PHASE SEQ
1
0 = DISABLE
1 = ENABLE
1
Indicates if drive and bypass
would run the motor in the same
direction.
Group 32: Supervisory Control
Code
Name
Resolution
Range
Default
Description
3201
SUPER CTRL
1
0 = DISABLE
1 = ENABLE
DISABLE
(0)
Enable supervisory control in
bypass mode.
3202
START LVL
1%
0 - 100%
70%
Value of drive's AI2 that causes
bypass contactor closure.
Applies only in supervisory mode.
3203
STOP LEVEL
1%
0 - 100%
30%
Value of drive's AI2 that causes
bypass contactor opening.
Applies only in supervisory mode.
3204
START DLY
1s
20 - 3600s
40s
Time that close condition must be
present before contactor is closed.
Applies only in supervisory mode.
3205
STOP DLY
1s
20 - 3600s
60s
Time that open condition must be
present before contactor is
opened.
Applies only in supervisory mode.
3206
FBK LOSS
1
0 = BYP STOP
1 = BYP START
BYP START
(1)
Bypass contactor operation if drive
link fault, drive AI2 loss or
excessive cycling.
Group 33: Information
Code
Name
Resolution
Range
Default
Description
3301
FW VERSION
hex
—
Revision of main application
firmware.
3302
PT VERSION
hex
—
Revision of panel text file.
3303
LP VERSION
—
—
Loading package version.
3304
CB VERSION
—
—
Control board version.
3305
TEST DATE
—
—
Summary of Contents for ACH580 Series
Page 2: ......
Page 11: ...ACH580 BCR BDR VCR VDR E Clipse Bypass Drives 1 200 HP ...
Page 35: ...26 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 43: ...34 ACH580 E Clipse bypass and packaged drive user manual Start up ...
Page 67: ...58 ACH580 E Clipse bypass and packaged drive user manual Application macros ...
Page 193: ...184 ACH580 E Clipse bypass and packaged drive user manual Fieldbus adapter ...
Page 207: ...198 ACH580 E Clipse bypass and packaged drive user manual Diagnostics ...
Page 229: ...220 ACH580 E Clipse bypass and packaged drive user manual Technical data ...
Page 231: ...ACH580 PCR PDR Packaged Drives with Disconnect 1 200 HP ...
Page 243: ...234 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 256: ......