ACH580 E-Clipse bypass and packaged drive user manual
89
Embedded fieldbus
Feedback from the drive – EFB
Pre-defined feedback
Inputs to the controller (drive outputs) have pre-defined meanings established by the
protocol. This feedback does not require drive configuration. The following table lists
a sample of feedback data. For a complete listing, see input word/point/object
listings in the technical data for the appropriate protocol starting on page
Note:
With Modbus, any parameter can be accessed using the format: 4 followed by
the parameter number. Example: (group #) * 256 + parameter#
Drive Parameter
Protocol Reference
Modbus
N2
BACnet
01.01
Motor Speed Used
400257
AI3
AV0
01.06
Output Frequency
400262
AI1
AV1
01.07
Motor Current
400263
AI4
AV4
01.10
Motor Torque
400266
AI5
AV5
01.14
Output Power
400270
AI6
AV6
01.11
DC Voltage
400267
AI11
AV2
01.13
Output Voltage
400269
AI12
AV3
01.57
Inverter KWH Counter (resettable)
400313
AI8
AV8
10.02
DI Delayed Status
402562
BI12
BI6
10.21
RO Status
402581
BI4, BI5, BI6
BI0
58.19
EFB Status Word – bit 0 (STOP)
414867 bit 0
BI1
BV0
58.19
EFB Status Word – bit 2 (REV)
414867 bit 2
BI2
BV1
Summary of Contents for ACH580 Series
Page 2: ......
Page 11: ...ACH580 BCR BDR VCR VDR E Clipse Bypass Drives 1 200 HP ...
Page 35: ...26 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 43: ...34 ACH580 E Clipse bypass and packaged drive user manual Start up ...
Page 67: ...58 ACH580 E Clipse bypass and packaged drive user manual Application macros ...
Page 193: ...184 ACH580 E Clipse bypass and packaged drive user manual Fieldbus adapter ...
Page 207: ...198 ACH580 E Clipse bypass and packaged drive user manual Diagnostics ...
Page 229: ...220 ACH580 E Clipse bypass and packaged drive user manual Technical data ...
Page 231: ...ACH580 PCR PDR Packaged Drives with Disconnect 1 200 HP ...
Page 243: ...234 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 256: ......