66
ACH580 E-Clipse bypass and packaged drive user manual
Parameters
1626
MODE LOCK
1
0 = NOT SEL
1 = AUTO MODE
2 = LOCAL MODE
NOT SEL
(0)
When Mode Lock is AUTO
MODE, the control panel will not
allow switching to Hand or Off.
When Mode Lock is LOCAL
MODE, the control panel will not
allow switching to Auto.
1627
COST/KWH
0.1 c/kWh
0.0 - 100.00 c/
kWh
7.0 c/kWh
Cost of energy: cents/kWh
1628
LEARN MODE
1
0 = NOT SEL
1 = ENABLED
NOT SEL
(0)
When enabled, bypass learns
average power consumption
while operating in bypass mode
1629
LEARN TIME
0.1 Hr
0.0 - 200.0 Hr
48.0 Hr
Time that learn mode will be
active after it is enabled
1630
START REV
0 = NOT SEL
1 = DI2
NOT SEL
(0)
• Selects source for drive start
reverse command for a
constant frequency for wiring
diagram above and
programming below.
• Reverse request can only be
selected for DI2 on the
E-Clipse
• Drive Param 20.21
(Direction) needs to be set for
REQUEST.
• Drive Param 28.22 (Constant
Frequency Sel 1) needs to be
set to DI3.
• Drive Param 28.26 (Constant
Frequency 1) needs to be set
for frequency required. Use
positive value.
• Drive Param 28.21 bit 1
(Direction enable) set to 1.
• When E-Clipse input DI2 is
energized the bypass sets
drive’s reverse run request
over the communication link.
• The same signal input for
bypass DI2 goes to Drive DI3
and sets constant frequency.
• The Reverse request has
priority over normal Run
input, this means that if
both DI1 and DI2 are closed
at the same time motor will
run reverse at the constant
frequency.
Group 16: System Control
Code
Name
Resolution
Range
Default
Description
Drve
ByPass
DI3
DComm
DComm
DI2
+24V
Rev Request
Summary of Contents for ACH580 Series
Page 2: ......
Page 11: ...ACH580 BCR BDR VCR VDR E Clipse Bypass Drives 1 200 HP ...
Page 35: ...26 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 43: ...34 ACH580 E Clipse bypass and packaged drive user manual Start up ...
Page 67: ...58 ACH580 E Clipse bypass and packaged drive user manual Application macros ...
Page 193: ...184 ACH580 E Clipse bypass and packaged drive user manual Fieldbus adapter ...
Page 207: ...198 ACH580 E Clipse bypass and packaged drive user manual Diagnostics ...
Page 229: ...220 ACH580 E Clipse bypass and packaged drive user manual Technical data ...
Page 231: ...ACH580 PCR PDR Packaged Drives with Disconnect 1 200 HP ...
Page 243: ...234 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 256: ......