ACH580 E-Clipse bypass and packaged drive user manual
Installation
• Use wire ties to permanently affix control/communications wiring to the hooked
wire race tie points provided maintaining a minimum 6 mm (1/4 in.) spacing from
power wiring.
• Use a separate motor conduit run for each motor.
Wiring overview
Connection and wiring diagrams – Vertical E-Clipse Bypass
ACH580 Vertical E-Clipse Bypass units are configured for wiring access from the
bottom only. The following figures show the layout and wiring connection points. For
drive control wiring, see page
. Maintain appropriate separation of control and
power wires.
Drive Control Panel
E-Clipse Bypass
Control Panel
Disconnect Switch
or Circuit Breaker
Motor
Input
Motor Ground
Lug
Terminals
Terminals
Input
Ground Lug
Service Switch
(Optional)
V1/V2
ACH580 Drive
E-Clipse Bypass
Control Board
Terminals (X2)
Fuses
(Vx1-1, Vx1-2)
Summary of Contents for ACH580 Series
Page 2: ......
Page 11: ...ACH580 BCR BDR VCR VDR E Clipse Bypass Drives 1 200 HP ...
Page 35: ...26 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 43: ...34 ACH580 E Clipse bypass and packaged drive user manual Start up ...
Page 67: ...58 ACH580 E Clipse bypass and packaged drive user manual Application macros ...
Page 193: ...184 ACH580 E Clipse bypass and packaged drive user manual Fieldbus adapter ...
Page 207: ...198 ACH580 E Clipse bypass and packaged drive user manual Diagnostics ...
Page 229: ...220 ACH580 E Clipse bypass and packaged drive user manual Technical data ...
Page 231: ...ACH580 PCR PDR Packaged Drives with Disconnect 1 200 HP ...
Page 243: ...234 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 256: ......