ACH580 E-Clipse bypass and packaged drive user manual
Embedded fieldbus
BV10
RUN/STOP CMD
This Object commands a system
start. This requires bypass
parameter 1601 value = COMM
for BACnet to control.
RUN/ STOP
C
BV11
OVERRIDE CMD
This Object commands the
system to an override 2
condition. This requires bypass
parameter 1701 value = COMM
for BACnet to control.
YES/NO
C
BV12
RUN
PERMISSIVE
CMD
This Object commands the
system Run Permissive. This
requires bypass parameter 1602
value = COMM for BACnet to
control.
ENABLE/
DISABLE
C
BV13
OVERRIDE ACT
This Object indicates if override
1 or override 2 is active
regardless of the control source.
YES/NO
R
BV14
FAULT RESET
This Object resets a faulted
bypass. This requires bypass
parameter 1607 value = COMM
for BACnet to control.
RESET/ NO
C
BV15
START
INTERLOCK 1
This Object commands the
system Start Interlock 1. This
requires bypass parameter 1603
value = COMM for BACnet to
control.
ENABLE/
DISABLE
C
BV16
START
INTERLOCK 2
This Object commands the
system Start Interlock 2. This
requires bypass parameter 1604
value = COMM for BACnet to
control.
ENABLE/
DISABLE
C
BV17
START
INTERLOCK 3
This Object commands the
system Start Interlock 3. This
requires bypass parameter 1605
value = COMM for BACnet to
control.
ENABLE/
DISABLE
C
BV18
START
INTERLOCK 4
This Object commands the
system Start Interlock 4. This
requires bypass parameter 1606
value = COMM for BACnet to
control.
ENABLE/
DISABLE
C
BV19
PAR LOCK
When switched to locked
prevents parameter changes
from the panel.
LOCK /
UNLOCK
W
BV20
CTL OVERRIDE
CMD
Commands the bypass into
BACnet Control Override. In this
mode, BACnet takes the bypass
control from the normal source.
However, the panel’s HAND
mode still has priority.
ON / OFF
C
BV21
MBOX READ
This object reads a parameter
(defined by AV13 MBOX
PARAM) and returns it in AV14
MBOX DATA
READ /
RESET
W
Instance
ID
Object Name
Description
Active/
Inactive Text
Present Value
Access Type
Summary of Contents for ACH580 Series
Page 2: ......
Page 11: ...ACH580 BCR BDR VCR VDR E Clipse Bypass Drives 1 200 HP ...
Page 35: ...26 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 43: ...34 ACH580 E Clipse bypass and packaged drive user manual Start up ...
Page 67: ...58 ACH580 E Clipse bypass and packaged drive user manual Application macros ...
Page 193: ...184 ACH580 E Clipse bypass and packaged drive user manual Fieldbus adapter ...
Page 207: ...198 ACH580 E Clipse bypass and packaged drive user manual Diagnostics ...
Page 229: ...220 ACH580 E Clipse bypass and packaged drive user manual Technical data ...
Page 231: ...ACH580 PCR PDR Packaged Drives with Disconnect 1 200 HP ...
Page 243: ...234 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 256: ......