ACH580 E-Clipse bypass and packaged drive user manual
23
Installation
Enabled
LED is not illuminated solid green, check to see that closed contacts or
jumpers connect terminal X2:3 to X2:4 and X2:2 to X2:7 on the bypass control
board.
5. On the E-Clipse Bypass control panel, either the
Drive Selected
or
Bypass Selected
LED should be illuminated. Pressing the
Drive Select
or
Bypass Select
key should
switch the bypass back and forth between the
Drive
mode and the
Bypass
mode as
indicated by the LEDs above each button. Check that the bypass control panel
switches the system between modes. Leave the system in the Bypass mode when
proceeding to the next step.
6. Check to see that pressing the:
•
Auto
key on the bypass control panel causes the bottom line on the E-Clipse
Bypass display to indicate “
Bypass in Auto
”.
•
Hand
key on the bypass control panel generates a Motor Phase Fault.
• Under normal conditions (motor connected) pressing the
Hand
key on the bypass
control panel causes the bottom line on the E-Clipse Bypass display to indicate
“Hand #A Run”.
•
OFF
key on the bypass control panel causes the bottom line on the E-Clipse
Bypass display to indicate “Off Stop”.
7. For Steps 8 through 14, ACH580 Drive Parameter 99.04 must be set to “Scalar”.
After successful completion of Step 13, Parameter 99.04 may be set to “Vector” if
very specific application requirements make it necessary to use this type of motor
control. Operation using the “Vector” setting is unnecessary for control of almost all
fan and pump applications. Refer to the
ACH580 firmware manual
(3AXD50000027537)
for details on setting parameters.
8. Press the
Drive Select
key on the E-Clipse Bypass control panel. The
Drive Select
LED should be illuminated.
9. Check to see that pressing the:
•
Auto
key on the bypass control panel causes the E-Clipse Bypass display to
indicate “
Bypass in Auto
”.
•
Hand
key on the bypass control panel causes no change to the E-Clipse Bypass
display.
•
OFF
key on the bypass control panel causes the E-Clipse Bypass display to
indicate “
Bypass in Off”.
10. Press the
HAND
key on the drive control panel. Note that the top line of the control
panel display indicates “HAND” and run as a clockwise rotating arrow. The
Drive
Run
LED on the E-Clipse Bypass control panel should be illuminated.
11. Press the
UP
arrow on the drive control panel. Note that the speed reference
indication in the top line of the drive control panel display increases from “0 HZ”.
12. In the middle line of the drive control panel display, the output current indication
should indicate “0.0 A.”
13. Press the
DOWN
arrow on the drive control panel until the speed and frequency
indications return to “0.0.”
Summary of Contents for ACH580 Series
Page 2: ......
Page 11: ...ACH580 BCR BDR VCR VDR E Clipse Bypass Drives 1 200 HP ...
Page 35: ...26 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 43: ...34 ACH580 E Clipse bypass and packaged drive user manual Start up ...
Page 67: ...58 ACH580 E Clipse bypass and packaged drive user manual Application macros ...
Page 193: ...184 ACH580 E Clipse bypass and packaged drive user manual Fieldbus adapter ...
Page 207: ...198 ACH580 E Clipse bypass and packaged drive user manual Diagnostics ...
Page 229: ...220 ACH580 E Clipse bypass and packaged drive user manual Technical data ...
Page 231: ...ACH580 PCR PDR Packaged Drives with Disconnect 1 200 HP ...
Page 243: ...234 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 256: ......