210
ACH580 E-Clipse bypass and packaged drive user manual
Technical data
E-Clipse Bypass control unit connections (RBCU)
Control cable requirements for connections to the E-Clipse Bypass (RBCU) (X2) are the
same as those described for the ACH580 control panel (X1). Refer to the
ACH580-01
Hardware Manual
(3AXD50000044839) for additional information.
Bypass control unit connection specifications
WARNING!
Relay coils generate noise spikes
in response to steps in applied power. To avoid
drive damage from such spikes, all AC relay
coils mounted across control panel inputs
require R-C snubbers, and all DC relay coils
mounted across control panel outputs require
diodes – see figure.
Bypass control unit terminals
The following table provides specifications for the E-Clipse Bypass’s control unit
terminals.
Control Connection Specifications
Digital Inputs
Digital input impedance 1.5 k
. Maximum voltage for digital inputs is 30 V AC/DC
Relays
(Digital Outputs)
• Max. contact voltage: 30 V DC, 250 V AC
• Max. contact current / power: 6 A, 30 V DC; 1500 VA, 250 V AC
• Max. continuous current: 2 A rms (cos . = 1), 1 A rms (cos. = 0.4)
• Minimum load: 500 mW (12 V, 10 mA)
• Contact material: Silver-nickel (AgN)
• Isolation between relay digital outputs, test voltage: 2.5 kV rms, 1 minute
Frame Size
Control
Maximum Wire Size
Torque
mm
2
AWG
N•m
lb-ft
All
0.12…2.5
26…14
0.4
0.3
33 Ohm
0.47 uF
AC Coil
Control
Typical R-C
Snubber
DC Coil
Diode
+
-
Panel
Inputs
Control
Panel
Outputs
Summary of Contents for ACH580 Series
Page 2: ......
Page 11: ...ACH580 BCR BDR VCR VDR E Clipse Bypass Drives 1 200 HP ...
Page 35: ...26 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 43: ...34 ACH580 E Clipse bypass and packaged drive user manual Start up ...
Page 67: ...58 ACH580 E Clipse bypass and packaged drive user manual Application macros ...
Page 193: ...184 ACH580 E Clipse bypass and packaged drive user manual Fieldbus adapter ...
Page 207: ...198 ACH580 E Clipse bypass and packaged drive user manual Diagnostics ...
Page 229: ...220 ACH580 E Clipse bypass and packaged drive user manual Technical data ...
Page 231: ...ACH580 PCR PDR Packaged Drives with Disconnect 1 200 HP ...
Page 243: ...234 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 256: ......