92
ACH580 E-Clipse bypass and packaged drive user manual
Embedded fieldbus
Miscellaneous system control
Note:
Control of system commands is dependent upon the setting of bypass
parameter 1625.
Using the fieldbus miscellaneous system control requires:
• Bypass parameter values set as defined below.
• Fieldbus controller supplied reference word(s) in the appropriate location. (The
location is defined by the Protocol Reference, which is protocol dependent.)
Bypass Parameter
Value
Setting
Protocol Reference
Modbus
N2
BACnet
1602
RUN
PERMISSIVE
2 (COMM)
(Not
Recommended)
Run permissive by
fieldbus.
400001 bit 2
BO2
BV12
1603
START
INTERLOCK 1
2 (COMM)
(Not
Recommended)
Source for Start
Interlock 1 is the
fieldbus
Command word.
400001 bit 4
BO10
BV15
1604
START
INTERLOCK 2
2 (COMM)
(Not
Recommended)
Source for Start
Interlock 2 is the
fieldbus
Command word.
400001 bit 5
BO11
BV16
1605
START
INTERLOCK 3
2 (COMM)
(Not
Recommended)
400001 bit 6
BO12
BV17
1606
START
INTERLOCK 4
2 (COMM)
(Not
Recommended)
400001 bit 7
BO13
BV18
1607
RESET SRC
2 (COMM)
Fault reset by
fieldbus
400001 bit 1
BO3
BV14
1625
COMM CTRL
1 (SYSTEM)
Enable System
Control.
N/A
Summary of Contents for ACH580 Series
Page 2: ......
Page 11: ...ACH580 BCR BDR VCR VDR E Clipse Bypass Drives 1 200 HP ...
Page 35: ...26 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 43: ...34 ACH580 E Clipse bypass and packaged drive user manual Start up ...
Page 67: ...58 ACH580 E Clipse bypass and packaged drive user manual Application macros ...
Page 193: ...184 ACH580 E Clipse bypass and packaged drive user manual Fieldbus adapter ...
Page 207: ...198 ACH580 E Clipse bypass and packaged drive user manual Diagnostics ...
Page 229: ...220 ACH580 E Clipse bypass and packaged drive user manual Technical data ...
Page 231: ...ACH580 PCR PDR Packaged Drives with Disconnect 1 200 HP ...
Page 243: ...234 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 256: ......