ACH580 E-Clipse bypass and packaged drive user manual
Embedded fieldbus
Status Word
The contents of the
STATUS
WORD
is status information, sent by the drive to the
master station.
ABB drives profile
The following table and the state diagram later in this sub-section describe the status
word content for the ABB Drives Profile.
29
LINK_ON
1
Master is detected
in link
0
Link is down
30
REQ_STARTINH
1
Start inhibit request
is pending
0
Start inhibit request
is OFF
ABB Drives Profile (EFB) STATUS WORD
Bit
Name
Value
Description
(Correspond to states/boxes in the state diagram)
0
RDY_ON
1
READY TO SWITCH ON
0
NOT READY TO SWITCH ON
1
RDY_RUN
1
READY TO OPERATE
0
OFF1 ACTIVE
2
RDY_REF
1
OPERATION ENABLED
0
OPERATION INHIBITED
3
TRIPPED
0…1
FAULT
0
No fault
4
OFF_2_STA
1
OFF2 INACTIVE
0
OFF2 ACTIVE
5
OFF_3_STA
1
OFF3 INACTIVE
0
OFF3 ACTIVE
6
SWC_ON_INHIB
1
SWITCH-ON INHIBIT ACTIVE
0
SWITCH-ON INHIBIT NOT ACTIVE
7
WARNING
1
in the
section for details on warnings.)
0
No warning/warning
8
AT_SETPOINT
1
OPERATING
.
Actual value equals (within tolerance limits)
the reference value.
0
Actual value is outside tolerance limits (not equal to
reference value).
9
REMOTE
1
Drive control location:
REMOTE
(EXT1 or EXT2)
0
Drive control location: LOCAL
DCU Profile CONTROL WORD
Bit
Name
Value
Function
Comments
Summary of Contents for ACH580 Series
Page 2: ......
Page 11: ...ACH580 BCR BDR VCR VDR E Clipse Bypass Drives 1 200 HP ...
Page 35: ...26 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 43: ...34 ACH580 E Clipse bypass and packaged drive user manual Start up ...
Page 67: ...58 ACH580 E Clipse bypass and packaged drive user manual Application macros ...
Page 193: ...184 ACH580 E Clipse bypass and packaged drive user manual Fieldbus adapter ...
Page 207: ...198 ACH580 E Clipse bypass and packaged drive user manual Diagnostics ...
Page 229: ...220 ACH580 E Clipse bypass and packaged drive user manual Technical data ...
Page 231: ...ACH580 PCR PDR Packaged Drives with Disconnect 1 200 HP ...
Page 243: ...234 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 256: ......