The following table summarizes the mapping between the system (parameters
and I/0) and Modbus reference space. For details, see
below.
Communication profiles
When communicating by Modbus, the drive supports multiple profiles for control and
status information. Bypass parameter 5825 (EFB CTRL PROFILE) selects the profile
used. If bypass parameter 1625 = (1) SYSTEM then the drive and bypass profile are
fixed ABB BYPASS PROFILE. See section Bypass Overview for ABB BYPASS
PROFILE
• ABB DRV LIM – The primary (and default) profile is the ABB DRV LIM profile,
which standardizes the control interface with ACH580 and ACH550 drive
products. This profile is based on the PROFIBUS interface, and is discussed in
detail in the following sections.
• DCU PROFILE – Another profile is called the DCU PROFILE. It extends the
control and status interface to 32 bits.
• ABB DRV FULL – This profile standardizes the control interface with the ACH580
and ACH550 drive products. This profile is also based on the PROFIBUS
interface, and supports two control word bits not supported by the ABB DRV LIM
profile.
Modbus addressing
With Modbus, each function code implies access to a specific Modbus reference set.
Thus, the leading digit is not included in the address field of a Modbus message.
Note:
The drive supports the zero-based addressing of the Modbus specification.
Holding register 400002 is addressed as 0001 in a Modbus message. Similarly,
coil 33 is addressed as 0032 in a Modbus message.
Refer again to the
above. The following sections describe, in
detail, the mapping to each Modbus reference set.
0xxxx Mapping – Modbus Coils.
The drive maps the following information to the
0xxxx Modbus set called Modbus Coils:
ACH580
Modbus Reference
Supported Function Codes
• Control Bits
• Relay Outputs
Coils(0xxxx)
• 01 – Read Coil Status
• 05 – Force Single Coil
• 15 – Force Multiple Coils
• Status Bits
• Discrete Inputs
Discrete Inputs(1xxxx)
• 02 – Read Input Status
• Analog Inputs
Input Registers(3xxxxx)
• 04 – Read Input Registers
• Parameters
• Control/Status Words
• References
Holding Registers(4xxxx)
• 03 – Read 4X Registers
• 06 – Preset Single 4X Register
• 16 – Preset Multiple 4X Registers
• 23 – Read/Write 4X Registers
Summary of Contents for ACH580 Series
Page 2: ......
Page 11: ...ACH580 BCR BDR VCR VDR E Clipse Bypass Drives 1 200 HP ...
Page 35: ...26 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 43: ...34 ACH580 E Clipse bypass and packaged drive user manual Start up ...
Page 67: ...58 ACH580 E Clipse bypass and packaged drive user manual Application macros ...
Page 193: ...184 ACH580 E Clipse bypass and packaged drive user manual Fieldbus adapter ...
Page 207: ...198 ACH580 E Clipse bypass and packaged drive user manual Diagnostics ...
Page 229: ...220 ACH580 E Clipse bypass and packaged drive user manual Technical data ...
Page 231: ...ACH580 PCR PDR Packaged Drives with Disconnect 1 200 HP ...
Page 243: ...234 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 256: ......