Communication Protocols
Value
Description
Default
Size
Menu path
NInternalError
Number of Internal Errors 0
0 - 9999999999
[Operation
/Count and RevData
/IEC 103]
NBadCharChecksum
Number of Checksum
Errors
0
0 - 9999999999
[Operation
/Count and RevData
/IEC 103]
IRIG-B00X
IRIG-B
Requirement: A IRIG-B00X time code receiver is needed. IRIG-B004 and
higher will support/transmit the “year” information.
If you are using an IRIG time code that does not support the “year”
information (IRIG-B000, IRIG-B001, IRIG-B002, IRIG-B003), you have to set
the “year” manually within the device. In these cases the correct year
information is a precondition for a properly working IRIG-B.
Please note, that the signal IRIG-B.active only becomes true, if the Function
is set to active and the device receives valid IRIG-B data.
Principle - General Use
This standard is the most used standard to synchronize the time of protection devices in medium voltage
applications.
Page 208
EN MRM4 01/11
IRIG-B
Time Code Generator
Protective Relay
GPS Satellite Signal (optional)
GPS Conncection (optional)
+
Twisted Pair Cable
To Other Devices
-