Field Parameters
Field Parameters
Field Para
Within the field parameters you can set all parameters, that are relevant for the primary side and the mains
operational method like frequency, primary and secondary values and the star point treatment.
General Field Parameters
Parameter
Description
Setting range
Default
Menu path
Phase Sequence
Phase Sequence
direction
ABC,
ACB
ABC
[Field Para
/General settings]
f
Nominal frequency
50Hz,
60Hz
50Hz
[Field Para
/General settings]
Field Parameters – Current Related
Parameter
Description
Setting range
Default
Menu path
CT pri
Nominal current of the
primary side of the
current transformers.
1 - 50000A
10A
[Field Para
/Current transf]
CT sec
Nominal current of the
secondary side of the
current transformers.
1A,
5A
1A
[Field Para
/Current transf]
CT dir
Protection functions with
directional feature can
only work properly if the
connection of the current
transformers is free of
wiring errors. If all
current transformers are
connected to the device
with an incorrect polarity,
the wiring error can be
compensated by this
parameter. This
parameter turns the
current vectors by 180
degrees.
0°,
180°
0°
[Field Para
/Current transf]
ECT pri
This parameter defines
the primary nominal
current of the connected
earth current transformer.
If the earth current is
measured via the
Holmgreen connection,
the primary value of the
phase current
transformer must be
entered here.
1 - 50000A
50A
[Field Para
/Current transf]
Page 234
EN MRM4 01/11
Содержание MRM4
Страница 1: ...MRM4 HighPROTEC Motor Protection Device Manual DOK HB MRM4E...
Страница 3: ...Order Code EN MRM4 01 11 Page 3...
Страница 18: ...Important Definitions Page 18 EN MRM4 01 11 41 SG Prot ON 42 SG ON Cmd SG Prot ON SG ON Cmd...
Страница 115: ...Navigation Operation Navigation Operation EN MRM4 01 11 Page 115 1 2 3 5 7 6 8 10 9...
Страница 162: ...Recorder Name Description I 2 TripCmd Signal Trip Command Page 162 EN MRM4 01 11...