Protective Elements
Parameter
Description
Setting range
Default
Menu path
Blo TripCmd
Permanent blocking of
the Trip Command of the
module/stage.
inactive,
active
inactive
[Protection Para
/<n>
/I-Prot
/IG[1]]
ExBlo TripCmd Fc
Activate (allow) or
inactivate (disallow)
blocking of the
module/stage. This
parameter is only
effective if a signal is
assigned to the
corresponding global
protection parameter. If
the signal becomes true,
those modules/stages
are blocked that are
parametrized "ExBlo
TripCmd Fc=active".
inactive,
active
inactive
[Protection Para
/<n>
/I-Prot
/IG[1]]
IG Source
Selection if measured or
calculated ground current
should be used.
calculated,
measured
measured
[Protection Para
/<n>
/I-Prot
/IG[1]]
Measuring method
Measuring method:
fundamental or rms
Fundamental,
True RMS
Fundamental
[Protection Para
/<n>
/I-Prot
/IG[1]]
IG>
If the pickup value is
exceeded, the
module/stage will be
started.
Only available if:
Characteristic = DEFT
Or Characteristic = INV.
0.02 - 20.00In
IG[1]: 1.00In
IG[2]: 0.02In
IG[3]: 0.02In
IG[4]: 0.02In
[Protection Para
/<n>
/I-Prot
/IG[1]]
EN MRM4 01/11
Page 339
Содержание MRM4
Страница 1: ...MRM4 HighPROTEC Motor Protection Device Manual DOK HB MRM4E...
Страница 3: ...Order Code EN MRM4 01 11 Page 3...
Страница 18: ...Important Definitions Page 18 EN MRM4 01 11 41 SG Prot ON 42 SG ON Cmd SG Prot ON SG ON Cmd...
Страница 115: ...Navigation Operation Navigation Operation EN MRM4 01 11 Page 115 1 2 3 5 7 6 8 10 9...
Страница 162: ...Recorder Name Description I 2 TripCmd Signal Trip Command Page 162 EN MRM4 01 11...