Protective Elements
%I2/I1> - Unbalanced Load [46]
Elements:
I2>[1] ,I2>[2]
The
I2>
Current Unbalance element works similar to the
V 012
Voltage Unbalance element. The positive and
negative sequence currents are calculated from the 3-phase currents. The Threshold setting defines a minimum
operating current magnitude of I2 for the 46 function to operate, which insures that the relay has a solid basis for
initiating a current unbalance trip. The »
%(I2/I1)«
setting is the unbalance trip pickup setting. It is defined by the
ratio of negative sequence current to positive sequence current »
%(I2/I1)«.
This function requires positive or negative sequence current magnitude above the threshold setting and the
percentage current unbalance above the »
%(I2/I1)«
setting before allowing a current unbalance trip. Therefore,
both the threshold and percent settings must be met for the specified Delay time setting before the relay initiates
a trip for current unbalance.
All elements are identically structured.