Supervision
Setting Group Parameters of the Trip Circuit Supervision
Parameter
Description
Setting range
Default
Menu path
Function
Permanent activation or
deactivation of
module/stage.
inactive,
active
inactive
[Protection Para
/<n>
/Supervision
/TCS]
ExBlo Fc
Activate (allow) or
inactivate (disallow)
blocking of the
module/stage. This
parameter is only
effective if a signal is
assigned to the
corresponding global
protection parameter. If
the signal becomes true,
those modules/stages
are blocked that are
parametrized "ExBlo
Fc=active".
inactive,
active
inactive
[Protection Para
/<n>
/Supervision
/TCS]
t-TCS
Tripping delay time of the
Trip Circuit Supervision
0.10 - 10.00s
0.2s
[Protection Para
/<n>
/Supervision
/TCS]
Trip Circuit Supervision Input States
Name
Description
Assignment via
Aux ON
Position indicator/check-back signal of the
CB (52a)
[Protection Para
/Global Prot Para
/Supervision
/TCS]
Aux OFF
Module input state: Position
indicator/check-back signal of the CB (52b)
[]
ExBlo1-I
Module input state: External blocking1
[Protection Para
/Global Prot Para
/Supervision
/TCS]
ExBlo2-I
Module input state: External blocking2
[Protection Para
/Global Prot Para
/Supervision
/TCS]
EN MRM4 01/11
Page 413
Содержание MRM4
Страница 1: ...MRM4 HighPROTEC Motor Protection Device Manual DOK HB MRM4E...
Страница 3: ...Order Code EN MRM4 01 11 Page 3...
Страница 18: ...Important Definitions Page 18 EN MRM4 01 11 41 SG Prot ON 42 SG ON Cmd SG Prot ON SG ON Cmd...
Страница 115: ...Navigation Operation Navigation Operation EN MRM4 01 11 Page 115 1 2 3 5 7 6 8 10 9...
Страница 162: ...Recorder Name Description I 2 TripCmd Signal Trip Command Page 162 EN MRM4 01 11...