Protective Elements
Parameter
Description
Setting range
Default
Menu path
ExBlo TripCmd Fc
Activate (allow) or
inactivate (disallow)
blocking of the
module/stage. This
parameter is only
effective if a signal is
assigned to the
corresponding global
protection parameter. If
the signal becomes true,
those modules/stages
are blocked that are
parametrized "ExBlo
TripCmd Fc=active".
inactive,
active
inactive
[Protection Para
/<n>
/I-Prot
/ThR]
Trip Function
Turn on or off the trip
function
inactive,
active
active
[Protection Para
/<n>
/I-Prot
/ThR]
Trip Threshold
Trip threshold at which
the thermal model will
trip, based on percentage
of thermal capacity used.
This value should
typically always be set at
0.99.
Only available if: Trip
Function = active.
0.60 - 0.99
0.99
[Protection Para
/<n>
/I-Prot
/ThR]
t-Trip Delay
Thermal capacity used
trip delay.
Only available if: Trip
Function = active.
0.0 - 3600.0s
0.0s
[Protection Para
/<n>
/I-Prot
/ThR]
Alarm Function
Turn on or off the alarm
function
inactive,
active
active
[Protection Para
/<n>
/I-Prot
/ThR]
Alarm Threshold
Alarm threshold at which
the thermal model will
trip, based on percentage
of thermal capacity used.
Only available if: Alarm
Function = active.
0.60 - 0.99
0.70
[Protection Para
/<n>
/I-Prot
/ThR]
t-Alarm Delay
Thermal capacity used
alarm delay.
Only available if: Alarm
Function = active.
1 - 360min
1min
[Protection Para
/<n>
/I-Prot
/ThR]
Page 390
EN MRM4 01/11
Содержание MRM4
Страница 1: ...MRM4 HighPROTEC Motor Protection Device Manual DOK HB MRM4E...
Страница 3: ...Order Code EN MRM4 01 11 Page 3...
Страница 18: ...Important Definitions Page 18 EN MRM4 01 11 41 SG Prot ON 42 SG ON Cmd SG Prot ON SG ON Cmd...
Страница 115: ...Navigation Operation Navigation Operation EN MRM4 01 11 Page 115 1 2 3 5 7 6 8 10 9...
Страница 162: ...Recorder Name Description I 2 TripCmd Signal Trip Command Page 162 EN MRM4 01 11...