Communication Protocols
The relay does not support functions to block the transmission in a certain direction (supervision direction).
Global Protection Parameters of the IEC60870-5-103
Parameter
Description
Setting range
Default
Menu path
Slave ID
Device address (Slave
ID) within the bus
system. Each device
address has to be unique
within a bus system.
01.01.47
1
[Device Para
/IEC 103]
t-call
If there is no request
telegram sent from
Scada to the device after
expiry of this time - the
device concludes a
communication failure
within the Scada system.
1 - 3600s
60s
[Device Para
/IEC 103]
Transm priv meas val
Transmit additional
(private) measuring
values.
inactive,
active
inactive
[Device Para
/IEC 103]
Baud rate
Baud rate
1200,
2400,
4800,
9600,
19200,
38400,
57600
19200
[Device Para
/IEC 103]
Physical Settings
Digit 1: Number of bits.
Digit 2: E=even parity,
O=odd parity, N=no
parity. Digit 3: Number of
stop bits. More
information on the parity:
It is possible that the last
data bit is followed by a
parity bit which is used
for recognition of
communication errors.
The parity bit ensures
that with even parity
("EVEN") always an even
number of bits with
valence "1" or with odd
parity ("ODD") an odd
number of "1" valence
bits are transmitted. But
it is also possible to
transmit no parity bits
(here the setting is "Parity
= None"). More
information on the stop-
bits: The end of a data
byte is terminated by the
stop-bits.
8E1,
8O1,
8N1,
8N2
8E1
[Device Para
/IEC 103]
Page 206
EN MRM4 01/11
Содержание MRM4
Страница 1: ...MRM4 HighPROTEC Motor Protection Device Manual DOK HB MRM4E...
Страница 3: ...Order Code EN MRM4 01 11 Page 3...
Страница 18: ...Important Definitions Page 18 EN MRM4 01 11 41 SG Prot ON 42 SG ON Cmd SG Prot ON SG ON Cmd...
Страница 115: ...Navigation Operation Navigation Operation EN MRM4 01 11 Page 115 1 2 3 5 7 6 8 10 9...
Страница 162: ...Recorder Name Description I 2 TripCmd Signal Trip Command Page 162 EN MRM4 01 11...