Communication Protocols
Value
Description
Default
Size
Menu path
Baud rate
The baud rate that has
been detected lastly, will
still be shown after a
connection issue.
-.-
12 Mb/s,
6 Mb/s,
3 Mb/s,
1.5 Mb/s,
0.5 Mb/s,
187500 baud,
93750 baud,
45450 baud,
19200 baud,
9600 baud,
-.-
[Operation
/Status display
/Profibus
/State]
PNO Id
PNO Identification
Number. GSD
Identification Number.
0C50h
0C50h
[Operation
/Status display
/Profibus
/State]
IEC60870-5-103
IEC 103
IEC60870-5-103 Protocol Configuration
In order to use the IEC60870-5-103 protocol it has to be assigned to the X103 Interface within the Device
Planning. The device will reboot after setting this parameter.
The parameter X103 is only available if the device is at the rear side
equipped with an interface like RS485 or Fiber Optic.
If the device is equipped with an Fiber Optic Interface, the Optical Rest
Position has to be set within the Device Parameters .
The time-controlled IEC60870-5-103 protocol is based on the Master-Slave working principle. This means that
the substation control and protection system sends an enquiry or instruction to a certain device (slave address)
which will then be answered or carried out accordingly.
The device meets the compatibility mode 2. Compatibility mode 3 is not supported.
The following IEC60870-5-103-functions will be supported:
•
Initialization (Reset);
•
Time Synchronization;
•
Reading out of time stamped, instantaneous signals;
•
General Queries;
•
Cyclic Signals;
•
General Commands; and
Page 204
EN MRM4 01/11
Содержание MRM4
Страница 1: ...MRM4 HighPROTEC Motor Protection Device Manual DOK HB MRM4E...
Страница 3: ...Order Code EN MRM4 01 11 Page 3...
Страница 18: ...Important Definitions Page 18 EN MRM4 01 11 41 SG Prot ON 42 SG ON Cmd SG Prot ON SG ON Cmd...
Страница 115: ...Navigation Operation Navigation Operation EN MRM4 01 11 Page 115 1 2 3 5 7 6 8 10 9...
Страница 162: ...Recorder Name Description I 2 TripCmd Signal Trip Command Page 162 EN MRM4 01 11...