Supervision
Device Planning Parameters of the Trip Circuit Supervision
Parameter
Description
Options
Default
Menu path
Mode
Mode
do not use,
use
use
[Device planning]
Global Protection Parameters of the Trip Circuit Supervision
Parameter
Description
Setting range
Default
Menu path
CB Pos Detect
Criterion by which the
Circuit Breaker Switch
Position is to be
detected.
-.-,
CB.Pos
-.-
[Protection Para
/Global Prot Para
/Supervision
/TCS]
Mode
Select if trip circuit is
going to be monitored
when the breaker is
closed or when the
breaker is either open or
close.
Closed,
Either
Closed
[Protection Para
/Global Prot Para
/Supervision
/TCS]
Input 1
Select the input
configured to monitor the
trip coil when the breaker
is closed.
-.-,
DI Slot X1.DI 1,
DI Slot X1.DI 2,
DI Slot X1.DI 3,
DI Slot X1.DI 4,
DI Slot X1.DI 1,
DI Slot X1.DI 2,
DI Slot X1.DI 3,
DI Slot X1.DI 4,
DI Slot X1.DI 5,
DI Slot X1.DI 6,
DI Slot X1.DI 7,
DI Slot X1.DI 8
-.-
[Protection Para
/Global Prot Para
/Supervision
/TCS]
ExBlo1
External blocking of the
module, if blocking is
activated (allowed) within
a parameter set and if the
state of the assigned
signal is true.
1..n, Assignment List
-.-
[Protection Para
/Global Prot Para
/Supervision
/TCS]
ExBlo2
External blocking of the
module, if blocking is
activated (allowed) within
a parameter set and if the
state of the assigned
signal is true.
1..n, Assignment List
-.-
[Protection Para
/Global Prot Para
/Supervision
/TCS]
Page 412
EN MRM4 01/11
Содержание MRM4
Страница 1: ...MRM4 HighPROTEC Motor Protection Device Manual DOK HB MRM4E...
Страница 3: ...Order Code EN MRM4 01 11 Page 3...
Страница 18: ...Important Definitions Page 18 EN MRM4 01 11 41 SG Prot ON 42 SG ON Cmd SG Prot ON SG ON Cmd...
Страница 115: ...Navigation Operation Navigation Operation EN MRM4 01 11 Page 115 1 2 3 5 7 6 8 10 9...
Страница 162: ...Recorder Name Description I 2 TripCmd Signal Trip Command Page 162 EN MRM4 01 11...