Protective Elements
Parameter
Description
Setting range
Default
Menu path
Dropout Threshold
Mechanical load
reclosure current
(Dropout of Load
shedding) as multiplier of
Ib.
0.50 - 1.50Ib
0.50Ib
[Protection Para
/<n>
/MLS]
t-Drop Delay
Dropout delay time
0.0 - 5.0s
1.0s
[Protection Para
/<n>
/MLS]
Load Shedding Input States
Name
Description
Assignment via
ExBlo1-I
Module input state: External blocking1
[Protection Para
/Global Prot Para
/MLS]
ExBlo2-I
Module input state: External blocking2
[Protection Para
/Global Prot Para
/MLS]
Load Shedding Signals (Output States)
Name
Description
active
Signal: active
ExBlo
Signal: External Blocking
Alarm
Signal: Alarm
Trip
Signal: Trip
Commissioning: Mechanical Load Shedding
Object to be tested:
•
Testing the pick-up and drop-out thresholds and
•
Testing the delay times.
Necessary means:
•
3-phase current source;
•
Ammeter; and
•
Timer for measuring of the tripping times.
Procedure
Testing the threshold values (three-phase)
This test is only possible, if the motor is in run mode.
Page 358
EN MRM4 01/11