Protective Elements
Parameter
Description
Setting range
Default
Menu path
EMGOVR
Emergency override
options. Signal has to be
active in order to release
the thermal capacity of
the motor. Please notice
that by doing this you run
the risk of damaging the
motor. “EMGOVR” has to
be set to “DI” or “DI or UI”
for this input to take
effect.
inactive,
DI,
HMI,
DI or HMI
inactive
[Protection Para
/Global Prot Para
/MStart
/Start Control]
Start Signal
Motor Start Signal. User
can tie a digital input to
this Input. If "Start-I"
becomes true,
"StartMotorCommand"
becomes true for at least
500ms.
-.-,
DI Slot X1.DI 1,
DI Slot X1.DI 2,
DI Slot X1.DI 3,
DI Slot X1.DI 4,
DI Slot X1.DI 1,
DI Slot X1.DI 2,
DI Slot X1.DI 3,
DI Slot X1.DI 4,
DI Slot X1.DI 5,
DI Slot X1.DI 6,
DI Slot X1.DI 7,
DI Slot X1.DI 8
-.-
[Protection Para
/Global Prot Para
/MStart
/Motor Inputs]
Stop
Stop Motor Signal
-.-,
DI Slot X1.DI 1,
DI Slot X1.DI 2,
DI Slot X1.DI 3,
DI Slot X1.DI 4,
DI Slot X1.DI 1,
DI Slot X1.DI 2,
DI Slot X1.DI 3,
DI Slot X1.DI 4,
DI Slot X1.DI 5,
DI Slot X1.DI 6,
DI Slot X1.DI 7,
DI Slot X1.DI 8
-.-
[Protection Para
/Global Prot Para
/MStart
/Motor Inputs]
EN MRM4 01/11
Page 277
Содержание MRM4
Страница 1: ...MRM4 HighPROTEC Motor Protection Device Manual DOK HB MRM4E...
Страница 3: ...Order Code EN MRM4 01 11 Page 3...
Страница 18: ...Important Definitions Page 18 EN MRM4 01 11 41 SG Prot ON 42 SG ON Cmd SG Prot ON SG ON Cmd...
Страница 115: ...Navigation Operation Navigation Operation EN MRM4 01 11 Page 115 1 2 3 5 7 6 8 10 9...
Страница 162: ...Recorder Name Description I 2 TripCmd Signal Trip Command Page 162 EN MRM4 01 11...