Smart View
Restoring of Device Data When Using Smart View
Via the button »Transfer only modified parameters into the device« only
modified parameters are transmitted into the device.
Parameter modifications are indicated by a red “star symbol” in front of the
parameter.
The star symbol (in the device tree window) indicates that parameters in the
opened file (within smart view) differ from parameters stored on your local
hard disk.
Via the button »Transfer only modified parameters into the device«, you can
transmit all parameters that are marked by this symbol.
If a parameter file is saved on your local hard drive, these parameters are
no longer classified to be modified and cannot be transmitted via the
button »Transfer only modified parameters into the device«.
In case that you have loaded and modified a parameter file from the device
and saved it to your local hard drive without transferring the parameters
into the device beforehand, you cannot use the button »Transfer only
modified parameters into the device«. In a case like that, use »Transfer all
parameters into the device«.
The button »Transfer only modified parameters into the device« only works
if modified parameters are available in the
Smart View
.
In contrast to that, all parameters of the device are transferred when the
button »Transfer all parameters into the device« is pressed (provided all
device parameters are valid).
•
In order to (re-)transfer changed parameters into the device, please select »Transfer all parameters into
the device« in menu »Device«.
•
Confirm the safety inquiry »Shall the parameters be overwritten into the device?“«.
•
Enter the password for setting parameters in the pop-up window.
•
Thereafter the changed data is transferred to the device and adopted.
•
Confirm the inquiry »Parameters successfully updated. It is recommended to save the parameters into a
local file on your hard drive. Shall The Data Be Saved Locally?“« with »Yes« (recommended). Select a
suitable folder on your hard disk.
•
Confirm the chosen folder by clicking »Save«.
•
The changed parameter data is now saved in the folder chosen by you.
Page 130
EN MRM4 01/11
Содержание MRM4
Страница 1: ...MRM4 HighPROTEC Motor Protection Device Manual DOK HB MRM4E...
Страница 3: ...Order Code EN MRM4 01 11 Page 3...
Страница 18: ...Important Definitions Page 18 EN MRM4 01 11 41 SG Prot ON 42 SG ON Cmd SG Prot ON SG ON Cmd...
Страница 115: ...Navigation Operation Navigation Operation EN MRM4 01 11 Page 115 1 2 3 5 7 6 8 10 9...
Страница 162: ...Recorder Name Description I 2 TripCmd Signal Trip Command Page 162 EN MRM4 01 11...