Input, Output and LED Settings
DI-4P X
DI Slot X1
Device Parameters of the Digital Inputs on DI-4P X
Parameter
Description
Setting range
Default
Menu path
Nom voltage
Nominal voltage of the
digital inputs
24 V DC,
48 V DC,
60 V DC,
110 V DC,
230 V DC,
110 V AC,
230 V AC
24 V DC
[Device Para
/Digital Inputs
/DI Slot X1]
Inverting 1
Inverting the input
signals.
inactive,
active
inactive
[Device Para
/Digital Inputs
/DI Slot X1]
Debouncing time 1
A change of the state of a
digital input will only be
recognized after the
debouncing time has
expired (become
effective). Thus,
transient signals will not
be misinterpreted.
no debouncing time,
20 ms,
50 ms,
100 ms
no debouncing time
[Device Para
/Digital Inputs
/DI Slot X1]
Inverting 2
Inverting the input
signals.
inactive,
active
inactive
[Device Para
/Digital Inputs
/DI Slot X1]
Debouncing time 2
A change of the state of a
digital input will only be
recognized after the
debouncing time has
expired (become
effective). Thus,
transient signals will not
be misinterpreted.
no debouncing time,
20 ms,
50 ms,
100 ms
no debouncing time
[Device Para
/Digital Inputs
/DI Slot X1]
Inverting 3
Inverting the input
signals.
inactive,
active
inactive
[Device Para
/Digital Inputs
/DI Slot X1]
Debouncing time 3
A change of the state of a
digital input will only be
recognized after the
debouncing time has
expired (become
effective). Thus,
transient signals will not
be misinterpreted.
no debouncing time,
20 ms,
50 ms,
100 ms
no debouncing time
[Device Para
/Digital Inputs
/DI Slot X1]
Page 62
EN MRM4 01/11
Содержание MRM4
Страница 1: ...MRM4 HighPROTEC Motor Protection Device Manual DOK HB MRM4E...
Страница 3: ...Order Code EN MRM4 01 11 Page 3...
Страница 18: ...Important Definitions Page 18 EN MRM4 01 11 41 SG Prot ON 42 SG ON Cmd SG Prot ON SG ON Cmd...
Страница 115: ...Navigation Operation Navigation Operation EN MRM4 01 11 Page 115 1 2 3 5 7 6 8 10 9...
Страница 162: ...Recorder Name Description I 2 TripCmd Signal Trip Command Page 162 EN MRM4 01 11...