Parameters
Operational Modes (Access Authorization)
Operational Mode – »Display Only«
•
The protection is activated.
•
All data, measuring values, records and counters/meters can be viewed.
Operation Mode – »Parameter Setting and Planning«
In this mode you are able to:
•
edit and set parameters;
•
change device planning details, and
•
parametrize and reset operational data (event recorder/fault recorder/power meter/switching cycles).
If the device was not active within the parameter setting mode for a longer
time (can be set between 20 – 3600 seconds) it changes automatically into
»Display Only« mode. (Please refer to the appendix
Module Panel
).
As long as you are within the parameter setting mode you cannot
acknowledge.
In order to change into operation mode »Parameter Setting« please proceed as follows:
1. Mark in the device display the parameter you want to change.
2. Press the softkey »Wrench« to change temporarily into the parameter setting mode.
3. Enter the parameter password.
4. Change the parameter.
5. Change perhaps additional parameters.
As long as you are within the parameter setting mode a wrench icon will be
shown in the upper right corner of the display.
6. For saving the altered parameter:
•
press the »OK« key and
•
confirm by pressing the softkey »Yes«.
7. Then the device changes into mode »Display Only«.
EN MRM4 01/11
Page 219
Содержание MRM4
Страница 1: ...MRM4 HighPROTEC Motor Protection Device Manual DOK HB MRM4E...
Страница 3: ...Order Code EN MRM4 01 11 Page 3...
Страница 18: ...Important Definitions Page 18 EN MRM4 01 11 41 SG Prot ON 42 SG ON Cmd SG Prot ON SG ON Cmd...
Страница 115: ...Navigation Operation Navigation Operation EN MRM4 01 11 Page 115 1 2 3 5 7 6 8 10 9...
Страница 162: ...Recorder Name Description I 2 TripCmd Signal Trip Command Page 162 EN MRM4 01 11...