Device
Device
MRM4
Device Planning
Planning of a device means to reduce the functional range to a degree that suits the protection task to be
fulfilled, i.e. the device shows only those functions you really need. If you, for example, deactivate the voltage
protection function, all parameter branches related to this function do not appear in the parameter tree any more.
All corresponding events, signals etc. will be deactivated too. By this the parameter trees become very
transparent. Planning also involves adjustment of all basic system data (frequency etc.).
But it has to be taken into account that by deactivating, for instance,
protective functions, you also change the functionality of the device. If you
cancel the directional feature of the overcurrent protections then the device
no longer trips in a directional way but merely in a non-directional way.
The manufacturer does not accept liability for any personal or material
damage as a result of wrong planning.
A planning service is also offered by
Woodward Kempen GmbH
.
Beware of inadvertent deactivating protective functions/modules
If you are deactivating modules within the device planning all parameters of
those modules will be set on default.
If you are activating one of these modules again all parameters of those
reactivated modules will be set on default.
EN MRM4 01/11
Page 21
Содержание MRM4
Страница 1: ...MRM4 HighPROTEC Motor Protection Device Manual DOK HB MRM4E...
Страница 3: ...Order Code EN MRM4 01 11 Page 3...
Страница 18: ...Important Definitions Page 18 EN MRM4 01 11 41 SG Prot ON 42 SG ON Cmd SG Prot ON SG ON Cmd...
Страница 115: ...Navigation Operation Navigation Operation EN MRM4 01 11 Page 115 1 2 3 5 7 6 8 10 9...
Страница 162: ...Recorder Name Description I 2 TripCmd Signal Trip Command Page 162 EN MRM4 01 11...