Installation and Connection
approx 3% of the rated current to ensure sufficient accuracy.
Example: For a 600 A CT (primary current) any currents below 18 A
cannot be detected any more.
•
Overloading can result in destruction of the measuring inputs or
faulty signals. Overloading means that in case of a short-circuit the
current-carrying capacity of the measuring inputs could be
exceeded.
Make sure, that the tightening torque is 2 Nm [17.7 In-lb].
EN MRM4 01/11
Page 39