Protective Elements
Direct Commands of the Motor Start Module
Parameter
Description
Setting range
Default
Menu path
EmergOver2UI
Emergency override
through front display
Only available if:
EMGOVR = active
inactive,
active
inactive
[Operation
/Reset
/EMGOVR]
RstForcedStart
Reset Forced Start flag
inactive,
active
inactive
[Operation
/Reset
/Flags]
Motor Start Module Counter Values
Value
Description
Default
Size
Menu path
WaitTimeStarts
Wait time between starts
remained
0s
0 - 9999999999s
[Operation
/Measured values
/Motor]
ColdStartPermit
Number of cold starts
remaining
0
0 - 9999999999
[Operation
/Measured values
/Motor]
StartPerHour
StartPerHour
0
0 - 9999999999
[Operation
/Measured values
/Motor]
AntiBackSpin
Anti-BackspinTimer
0s
0 - 9999999999s
[Operation
/Measured values
/Motor]
IL1 Ib
Measured value: Phase
current as percentage of
Ib
0Ib
0 - 1000Ib
[Operation
/Measured values
/Current RMS]
IL2 Ib
Measured value: Phase
current as percentage of
Ib
0Ib
0 - 1000Ib
[Operation
/Measured values
/Current RMS]
IL3 Ib
Measured value: Phase
current as percentage of
Ib
0Ib
0 - 1000Ib
[Operation
/Measured values
/Current RMS]
I3 P (%Ib) avg
Average RMS current of
all 3 phases as
percentages of Ib
0Ib
0 - 1000Ib
[Operation
/Measured values
/Current RMS]
Page 284
EN MRM4 01/11
Содержание MRM4
Страница 1: ...MRM4 HighPROTEC Motor Protection Device Manual DOK HB MRM4E...
Страница 3: ...Order Code EN MRM4 01 11 Page 3...
Страница 18: ...Important Definitions Page 18 EN MRM4 01 11 41 SG Prot ON 42 SG ON Cmd SG Prot ON SG ON Cmd...
Страница 115: ...Navigation Operation Navigation Operation EN MRM4 01 11 Page 115 1 2 3 5 7 6 8 10 9...
Страница 162: ...Recorder Name Description I 2 TripCmd Signal Trip Command Page 162 EN MRM4 01 11...