Protective Elements
Parameter
Description
Setting range
Default
Menu path
t
Tripping delay
Only available if:
Characteristic = DEFT
0.00 - 300.00s
I[1]: 0.50s
1.00s
1.00s
1.00s
1.00s
I[2]: 0.0s
1.00s
1.00s
1.00s
1.00s
I[3]: 1.00s
I[4]: 1.00s
I[5]: 1.00s
I[6]: 1.00s
[Protection Para
/<n>
/I-Prot
/I[1]]
t-char
Time multiplier/tripping
characteristic factor. The
setting range depends on
the selected tripping
curve.
Only available if:
Characteristic = INV Or
Characteristic = Therm
Flat Or Characteristic =
IT Or Characteristic =
I2T Or Characteristic =
I4T.
0.02 - 20.00
1
[Protection Para
/<n>
/I-Prot
/I[1]]
Reset Mode
Reset Mode
Only available if:
Characteristic = INV Or
Characteristic = Therm
Flat Or Characteristic =
IT Or Characteristic =
I2T Or Characteristic =
I4T.
instantaneous,
t-delay,
calculated
instantaneous
[Protection Para
/<n>
/I-Prot
/I[1]]
t-reset
Reset time for
intermittent phase
failures (INV
characteristics only).
Available if:Reset Mode
= t-delay.
0.00 - 60.00s
0s
[Protection Para
/<n>
/I-Prot
/I[1]]
EN MRM4 01/11
Page 307
Содержание MRM4
Страница 1: ...MRM4 HighPROTEC Motor Protection Device Manual DOK HB MRM4E...
Страница 3: ...Order Code EN MRM4 01 11 Page 3...
Страница 18: ...Important Definitions Page 18 EN MRM4 01 11 41 SG Prot ON 42 SG ON Cmd SG Prot ON SG ON Cmd...
Страница 115: ...Navigation Operation Navigation Operation EN MRM4 01 11 Page 115 1 2 3 5 7 6 8 10 9...
Страница 162: ...Recorder Name Description I 2 TripCmd Signal Trip Command Page 162 EN MRM4 01 11...