Input, Output and LED Settings
Parameter
Description
Setting range
Default
Menu path
Force OR5
By means of this function
the normal Output Relay
State can be overwritten
(forced). The relay can
be set from normal
operation (relay works
according to the assigned
signals) to "force
energized" or "force de-
energized" state.
Normal,
De-Energized,
Energized
Normal
[Service
/Test
/Force OR
/BO-5 X2]
Force OR6
By means of this function
the normal Output Relay
State can be overwritten
(forced). The relay can
be set from normal
operation (relay works
according to the assigned
signals) to "force
energized" or "force de-
energized" state.
Normal,
De-Energized,
Energized
Normal
[Service
/Test
/Force OR
/BO-5 X2]
Device Parameters of the Binary Output Relays on OR-5 X
Parameter
Description
Setting range
Default
Menu path
t-hold
To clearly identify the
state transition of a
binary output relay, the
"new state" is being hold,
at least for the duration of
the hold time.
0.00 - 300.00s
0.00s
[Device Para
/Binary Outputs
/BO-5 X2
/BO 1]
t-Off Delay
Switch Off Delay
0.00 - 300.00s
0.00s
[Device Para
/Binary Outputs
/BO-5 X2
/BO 1]
Latched
Defines whether the
Relay Output will be
latched when it picks up.
inactive,
active
active
[Device Para
/Binary Outputs
/BO-5 X2
/BO 1]
Page 68
EN MRM4 01/11
Содержание MRM4
Страница 1: ...MRM4 HighPROTEC Motor Protection Device Manual DOK HB MRM4E...
Страница 3: ...Order Code EN MRM4 01 11 Page 3...
Страница 18: ...Important Definitions Page 18 EN MRM4 01 11 41 SG Prot ON 42 SG ON Cmd SG Prot ON SG ON Cmd...
Страница 115: ...Navigation Operation Navigation Operation EN MRM4 01 11 Page 115 1 2 3 5 7 6 8 10 9...
Страница 162: ...Recorder Name Description I 2 TripCmd Signal Trip Command Page 162 EN MRM4 01 11...