Input, Output and LED Settings
Parameter
Description
Setting range
Default
Menu path
Force Mode
By means of this function
the normal Output Relay
States can be overwritten
(forced) in case that the
Relay is not in a
disarmed state. The
relays can be set from
normal operation (relay
works according to the
assigned signals) to
"force energized" or
"force de-energized"
state.
permanent,
Timeout
permanent
[Service
/Test
/Force OR
/OR-3AI X2]
t-Timeout Force
The Output State will be
set by force for the
duration of this time. That
means for the duration of
this time the Output
Relay does not show the
state of the signals that
are assigned on it.
Only available if: Mode =
Timeout DISARM
0.00 - 300.00s
0.03s
[Service
/Test
/Force OR
/OR-3AI X2]
Input States of the Binary Output Relays on OR- 3AI X
Name
Description
Assignment via
BO1.1
Module input state: Assignment
[Device Para
/Binary Outputs
/OR-3AI X2
/BO 1]
BO1.2
Module input state: Assignment
[Device Para
/Binary Outputs
/OR-3AI X2
/BO 1]
BO1.3
Module input state: Assignment
[Device Para
/Binary Outputs
/OR-3AI X2
/BO 1]
BO1.4
Module input state: Assignment
[Device Para
/Binary Outputs
/OR-3AI X2
/BO 1]
EN MRM4 01/11
Page 95
Содержание MRM4
Страница 1: ...MRM4 HighPROTEC Motor Protection Device Manual DOK HB MRM4E...
Страница 3: ...Order Code EN MRM4 01 11 Page 3...
Страница 18: ...Important Definitions Page 18 EN MRM4 01 11 41 SG Prot ON 42 SG ON Cmd SG Prot ON SG ON Cmd...
Страница 115: ...Navigation Operation Navigation Operation EN MRM4 01 11 Page 115 1 2 3 5 7 6 8 10 9...
Страница 162: ...Recorder Name Description I 2 TripCmd Signal Trip Command Page 162 EN MRM4 01 11...